Details of AC032S \ ecomat 300 \ AS-i (Safety Enhancing Device for AS-interface system) enhan. net \ DE
AC032S \ ecomat 300 \ AS-i (Safety Enhancing Device for AS-interface system) enhan. net \ DE is a tool for safely monitoring protection systems that can be used with various AS-interface devices
Technical Data AC032S \ ecomat 300 \ AS-i (Safety Enhancing Device for AS-interface system) enhan. net \ DE
Electrical design 1 safety-related output
Operating voltage [V] 24 DC ± 15%
Current consumption [mA]< 45
Peak switch-on current **) [mA] 600
Overvoltage category 3, for rated operating voltage 300 V AC to VDE 0110 part 1
Rated operating current [mA] 250
Input current High/Low [mA] 10 (24 V DC) / -
start input: optocoupler input (high active), input current approx. 10 mA (24 V DC)
contactor control input (EDM): optocoupler input (high active), input current approx. 10 mA (24 V DC)
Message output Safety ON ***) PNP transistor output/ 200 mA / reverse polarity and short-circuit protection
Safety output 2 volt-free NO contacts
max. contact load: 1 A DC-13 (24 V DC) / 3 A AC-15 (230 V AC)
continuous thermal current: 3 A per output circuit
Configuration interface 9600 baud / no parity / 1 start bit / 1 stop bit / 8 data bits