SANGI ELECTRIC Inverter Model SG-VB-4T160G/185P (Industrial Variable Frequency Drive)
SANGI ELECTRIC SG-VB-4T160G/185P is an inverter or Variable Frequency Drive (VFD) from the SG-VB Series designed to control the speed of three-phase AC motors by adjusting the output frequency and voltage to match the motor's operational characteristics.
The model code SG-VB-4T160G/185P corresponds to the base model VB-4T160G/185P, which specifies power ratings of 160 kW for G Type and 185 kW for P Type. It is suitable for consideration in high-power motor systems, but actual selection should be confirmed based on the power rating and current from the SANGI ELECTRIC product nameplate.
The SG-VB Series supports V/F Control and Torque Control modes along with RS485 Modbus communication for connecting to PLCs, HMIs, or other automation control systems that support the same protocol.
It can be applied in water pump systems, industrial fans, AHU systems, conveyor belts, and motor-driven machinery requiring speed control according to production process requirements.
General Features (Features)
- Brand: SANGI ELECTRIC
- Model: SG-VB-4T160G/185P
- Series: SG-VB Series
- Type: Industrial Inverter / Variable Frequency Drive
- For controlling three-phase AC motors
- Rated power 160 kW for G Type
- Rated power 185 kW for P Type
- Suitable for 3 Phase 380 VAC electrical systems as per SG-VB Series data
- Supports V/F Control mode
- Supports Torque Control mode
- Supports RS485 Modbus Communication
- Supports Digital Input and Analog Input connections as per SG-VB Series data
- Able to handle overloading according to G Type and P Type selections
- Suitable for motor control in factory automation systems
Technical Specifications (Technical Specifications)
| Specifications | Details |
| Brand | SANGI ELECTRIC |
| Model | SG-VB-4T160G/185P |
| Series | SG-VB |
| Product Type | Industrial Inverter / Variable Frequency Drive |
| Motor Type | Three-Phase AC Motor |
| G Type Motor Power | 160 kW (Matching VB Series Reference) |
| P Type Motor Power | 185 kW (Matching VB Series Reference) |
| Power Capacity G/P | 231 / 245 kVA (Matching VB Series Reference) |
| Input Phase | 3 Phase |
| Nominal Input Voltage | 380 VAC (SG-VB Series) |
| Input Voltage Tolerance | ±15% (SG-VB Series) |
| Input Frequency | 50/60 Hz ±15% (SG-VB Series) |
| Rated Input Current G/P | 307 / 345 A (Matching VB Series Reference) |
| Output Voltage | 3 Phase 0-380 VAC (SG-VB Series) |
| Rated Output Current G/P | 304 / 340 A (Matching VB Series Reference) |
| Control Method | V/F Control / Torque Control |
| V/F Output Frequency | 0-1000 Hz (SG-VB Series) |
| SVC Output Frequency | 0-320 Hz (SG-VB Series) |
| G Type Starting Torque | 150% at 0.5 Hz (SVC, SG-VB Series) |
| P Type Starting Torque | 100% at 0.5 Hz (SG-VB Series) |
| G Type Overload Capacity | 150% for 60 s / 180% for 1 s |
| P Type Overload Capacity | 120% for 60 s / 150% for 1 s |
| Digital Inputs | 6 Channels, NPN (SG-VB Series) |
| Analog Inputs | 2 Channels, 0-10 V / 4-20 mA (SG-VB Series) |
| Digital Outputs | Relay Contact NO/NC and NPN Output (SG-VB Series) |
| Analog Output | 1 Channel, 0-10 V / 4-20 mA (SG-VB Series) |
| Communication | RS485 Modbus |
| Protection Class | IP20 (Matching VB Series Reference) |
| Reference Dimensions | To Be Confirmed for SANGI ELECTRIC Model |
| Reference Weight | To Be Confirmed for SANGI ELECTRIC Model |
| Exact SANGI Nameplate Ratings | To Be Confirmed Before Ordering |
| Catalog Reference | SCMA General Catalog Vol.5, D4-01 to D4-04 |
Note on Data: The voltage, control system, signal channels, and communication are general specifications of the SG-VB Series as per the SCMA catalog. However, the power rating of 160/185 kW, current of 307/345 A, and 304/340 A refer to VB-4T160G/185P with matching codes but still need confirmation from SANGI ELECTRIC's datasheet or nameplate.
Motor Speed Control
The SG-VB Series inverter controls the speed of three-phase AC motors by adjusting the output frequency and voltage to match the machinery requirements, allowing users to set speeds according to process characteristics.
It can be applied to equipment requiring speed control such as water pumps, fans, and conveyor belts. Energy savings depend on the type of load and the method of control selected.
G Type and P Type Power Ratings
The basic model VB-4T160G/185P with matching power codes specifies motor ratings of 160 kW for G Type and 185 kW for P Type, with different current values according to usage.
| Rating | G Type | P Type |
| Motor Power | 160 kW | 185 kW |
| Power Capacity | 231 kVA | 245 kVA |
| Reference Input Current | 307 A | 345 A |
| Reference Output Current | 304 A | 340 A |
| Overload Capacity (60 s) | 150% | 120% |
| Overload Capacity (1 s) | 180% | 150% |
G Type is suitable for consideration with loads that require high overload capacity, while P Type is appropriate for loads that match the power and current ratings of the model, such as properly designed water pump or fan systems.
The motor current, starting torque, and Duty Cycle must be checked before selecting a model; kW power alone should not be used to make decisions.
V/F Control
SG-VB Series supports V/F Control for managing the relationship between voltage and frequency supplied to the motor to adjust speed according to system requirements.
The settings should refer to the motor nameplate data, rated frequency, rated voltage, and load characteristics to ensure control meets machine specifications.
Torque Control
SG-VB Series supports Torque Control for use in systems requiring torque control based on operating conditions. The setup method and limitations must be checked from the manufacturer's manual.
RS485 Modbus Communication
The SG-VB Series inverters support RS485 Modbus communication to connect with PLC, HMI, or external control systems that support the same protocol.
The Register Map, Baud Rate, Address, and Data Format should be checked from the manufacturer's manual before connecting. Proper wiring of RS485 and noise protection must also be ensured.
Digital and Analog Signal Channels
According to SG-VB Series data, there are 6 NPN-type Digital Inputs and 2 Analog Inputs for receiving signals in 0-10 V or 4-20 mA ranges, along with outputs used for status indication or external control signaling.
The signal ratings and terminal assignments of the actual model must be checked before designing circuits.
Overload Capability
| Operating Type | 60 Seconds | 1 Second |
| G Type | 150% Rated Current | 180% Rated Current |
| P Type | 120% Rated Current | 150% Rated Current |
The overload capacity values are from the SG-VB Series catalog and must be checked with test conditions, power derating, and additional time operation requirements.
Dimensions and Installation
The dimensions and weight of SG-VB-4T160G/185P must be confirmed from the Dimension Drawing or Datasheet of SANGI ELECTRIC, as the basic model VB information found has different dimensional details across some sources.
Control cabinet design should allow for heat dissipation space, power wiring space, and maintenance access according to the manufacturer's manual.
Braking System
For high-power inverters, it is necessary to check the requirement of using an External Braking Unit and a Braking Resistor based on load type and manufacturer specifications.
The Braking Resistor should not be directly connected to the DC Bus unless specified in the manual that the model supports this. Always verify the Wiring Diagram and component locations before installation.
Applications
- Three-phase motor speed control system
- High-power water pump systems in industrial plants
- Industrial fans and ventilation systems
- AHU and industrial air conditioning systems
- Belt conveyor systems with suitable load ratings
- Large machinery control systems
- Inverter control through PLC or HMI
- Factory Automation and Process Control Systems
Selecting SG-VB-4T160G/185P Guidelines
- Check the model number and power from the Nameplate of SANGI ELECTRIC
- Verify motor power at 160 kW or 185 kW based on load type
- Confirm three-phase input electrical system
- Compare motor rated current with inverter output current
- Consider differences between G Type and P Type
- Evaluate starting torque and acceleration performance
- Check RS485 Modbus compatibility
- Verify installation space and cooling systems
- Review necessary protective devices and braking systems
- Examine the Datasheet and Wiring Diagram before ordering
Installation Precautions
- Hire qualified electrical personnel for installation and inspection
- Verify number of phases and voltage before energizing
- Select wiring and protective devices according to actual equipment current ratings
- Install grounding wires as per standards and manufacturer requirements
- Properly allocate heat dissipation space suitable for high-power inverters
Separate the motor power cables from signal and communication lines
Check motor wiring to terminals U, V, and W according to the Wiring Diagram
Set motor parameters correctly before running
Select external brake equipment as per manual if required by the system
Design Emergency Stop and Safety circuits appropriately for machine risk level
Turn off power, lock source, and check that DC Bus has no voltage before maintenance
Important Notes Before Purchase (Important Notes)
- The product is the SANGI ELECTRIC inverter model SG-VB-4T160G/185P
- Belonging to the SG-VB Series
- Power 160/185 kW is reference data from the VB-4T160G/185P model
- Suitable for V/F Control and Torque Control according to SG-VB Series information
- Supports RS485 Modbus
- Incoming current 307/345 A and outgoing current 304/340 A are data from the comparable VB model
- The size and weight of the SANGI ELECTRIC specific model must be confirmed from manufacturer documentation
- Must check Nameplate and Datasheet of SANGI ELECTRIC before purchasing
- Motor compatibility with accessories must be checked before installation