SANGI SG-QTLD-DN150 Electromagnetic Flow Meter
SANGI SG-QTLD-DN150 is an electromagnetic flow meter in the SG-QTLD Series designed for measuring the flow rate of electrically conductive liquids. It is suitable for water supply systems, wastewater treatment systems, water distribution systems, and industrial manufacturing processes.
The SG-QTLD-DN150 model is a flowmeter for DN150 pipe size or approximately 6 inches in diameter. It operates on the principle of electromagnetic induction by measuring the electrical signal generated when electrically conductive liquids pass through an electromagnetic field, which is then processed to determine the flow rate.
This measurement method does not require rotating blades or mechanical parts within the flow path for measurement, thus reducing maintenance related to moving parts and making it ideal for continuous flow monitoring processes.
The SG-QTLD Series offers analog output signal options of 4-20mA, pulse output, and communication protocols such as Modbus-RS485, HART, or Profibus depending on the sub-model. This allows the flow rate data to be integrated with PLCs, HMIs, SCADA systems, and production control systems.
The SG-QTLD-DN150 model published by SCMA, with code SG-QTLD-DN150(6")-S1-P3-L4-E3-K1-F2-D1-G1-G2-C4-F1, is a Compact Type using Liner Neoprene (CR), Electrode Hastelloy C, and Cast Iron housing with JIS flange connections.
General Features
- SANGI flow meter brand
- SG-QTLD-DN150 model in the SG-QTLD Series
- Type: Electromagnetic Flow Meter
- Pipe size DN150 or approximately 6 inches
- Metering principle: Electromagnetic Induction
- Suitable for liquids with appropriate electrical conductivity values
- No rotating blades in the flow path
- Flow velocity range of Series 0.1-15 m/s
- Standard accuracy of Series ±0.5%
- Precision options of ±0.3% or ±0.2%
- Compact Type sub-model available
- Analog output signal option of 4-20mA depending on the sub-model
- Pulse output option depending on the sub-model
- Modbus communication protocol support depending on the sub-model
- Metal and flange standard options according to order code
- Suitable for water systems, wastewater treatment systems, and process control applications
Technical Specifications
| Specifications | Details |
| Brand | SANGI |
| Model | SG-QTLD-DN150 |
| Series | SG-QTLD |
| Product Type | Electromagnetic Flow Meter |
| Measuring Principle | Electromagnetic Induction |
| Nominal Pipe Size | DN150 (6 Inch) |
| Measured Medium | Electrically Conductive Liquids |
| Series Flow Velocity Range | 0.1-15 m/s |
| Standard Accuracy | ±0.5% (Series Specification) |
| Optional Accuracy | ±0.3% / ±0.2% (Depending on Configuration) |
| Minimum Liquid Conductivity | >5 µS/cm |
| Demineralized Water Conductivity | >20 µS/cm |
| Reference Structure | Compact Type |
| Reference Maximum Working Pressure | 1.6 MPa |
| Reference Medium Temperature | -10 to +80 °C |
| Reference Liner Material | Neoprene (CR) |
| Reference Electrode Material | Hastelloy C |
| Reference Body Material | Cast Iron |
| Reference Flange Options | JIS 10K / 20K / 40K (F2 Configuration) |
| Reference Power Supply | AC 85-250 V |
| Reference Analog Output | 4-20mA |
| Reference Pulse Output | Available |
| Reference Communication | Modbus |
| Reference Protection Degree | IP65 |
| Full Reference Model | SG-QTLD-DN150(6")-S1-P3-L4-E3-K1-F2-D1-G1-G2-C4-F1 |
| Catalog Reference | SCMA General Catalog Vol.5, E6-01 |
Note: The specified reference data is specific to the sub-model DN150 type F2 found from SCMA. Other SG-QTLD-DN150 codes may have different flange standards, materials, and installation patterns. It's necessary to check the full model code before ordering.
Working Principle of Electromagnetic Flow Meter
The Electromagnetic Flow Meter operates according to Faraday's Law of Electromagnetic Induction by creating a magnetic field through the measuring pipe where electrically conductive liquid flows.
When the liquid moves through the magnetic field, an electrical voltage proportional to the flow velocity is generated. The electrodes inside the meter detect this signal and send it to the processing circuit for calculation as the fluid flow rate.
This technology does not have rotating blades in the flow path, which helps reduce wear issues of rotating parts compared to some mechanical meters.
Pipe Size DN150 (Nominal Pipe Diameter)
The SG-QTLD-DN150 is a pipe size DN150 or approximately 6 inches meter suitable for installation in piping systems that match the meter's size and flange standard.
The referenced sub-model F2 has JIS 10K, 20K, and 40K flange options which must be selected to match the system pipe flanges before ordering. The mounting hole spacing, pressure rating, and Face-to-Face distance should also be checked from the Dimension Drawing.
Flow Measurement Range
The SG-QTLD Series specifies a flow velocity range of 0.1-15 m/s which is information for selecting meter size and operating range.
The actual measurable flow rate range depends on the internal cross-sectional area of the pipe and the measurement range setting of the unit, so it's necessary to check the minimum, normal, and maximum system flow rates before selection.
Measurement Accuracy
The SG-QTLD Series has a standard accuracy of ±0.5% with options for ±0.3% or ±0.2%, depending on model specification and calibration conditions.
The Calibration Certificate and certified measurement range should be checked if high accuracy is required in use.
Liquid Conductivity
SG-QTLD Series supports liquids with a conductivity of more than 5 µS/cm and for Demineralized Water, it specifies that the value must be greater than 20 µS/cm.
Not suitable for non-conductive liquids such as fuel oil, lubricating oil, and general hydrocarbons.
Neoprene (CR) Liner Material
The referenced sub-model DN150 uses Neoprene (CR) liner material which SCMA specifies is suitable for wastewater or water with high sediment content under the conditions of use of the material.
The liquid temperature range for the referenced sub-model is -10 to +80 °C, chemical compatibility and actual operating temperatures must be verified before selection.
Hastelloy C Electrode Material
The referenced sub-model DN150 uses Hastelloy C electrode material for detecting electrical signals generated by liquid flowing through a magnetic field.
Hastelloy C has corrosion-resistant properties in various conditions, but it should not be assumed to be suitable for all chemicals. The type of chemical, concentration and temperature must be verified as appropriate before selection.
4-20mA Output Signal
The referenced sub-model DN150 supports Analog Output 4-20mA for sending flow rate values to PLC, HMI, Data Logger and other control systems that support it.
Before use, the type of output, wiring method, and scaling value should be verified according to the flow rate range specified in the meter.
Pulse Output
The referenced sub-model DN150 supports Pulse Output for sending pulse signals to counting devices or control systems to calculate cumulative flow volume based on Pulse Scaling values.
Signal output coordinates, maximum frequency, and wiring requirements must be verified according to the manufacturer's manual.
Modbus Communication
The referenced sub-model DN150 supports Modbus for sending data to PLC, HMI, and SCADA systems that support the same protocol.
The type of Modbus interface, Register Map, Device Address, Baud Rate, and Parity should be verified according to the actual device manual before connecting.
Power Supply
The referenced sub-model DN150 uses AC 85-250 V power supply which must be checked against the Nameplate voltage rating before connection.
The SG-QTLD Series has DC power supply options for some models, so it should not be assumed that other model specifications can be used without verification.
IP65 Protection Level
The DN150 Compact Type sub-model with an IP65 protection level is suitable for installation in industrial environments as per the manufacturer's conditions.
Installation must properly seal cable entry points and select mounting positions that align with the equipment’s protection level.
Pipe System Installation (Installation)
The Electromagnetic Flow Meter should be installed at a position where there is full pipe cross-section liquid during measurement, avoiding areas prone to air bubble accumulation or incomplete liquid flow in the pipe.
Proper straight pipe runs before and after the meter as per the selected model's manual must be ensured, along with appropriate grounding and electrical bonding to help reduce the impact of electrical interference signals.
Application Examples (Applications)
- Potable water systems and water supply systems
- Sewage treatment systems
- Liquid systems that meet liner material requirements for sediment content
- Pump stations and water pumping systems
- Water circulation systems in industrial plants
- Flow rate measurement systems in production processes
- Pipe systems of conductive liquids
- Control through PLC and HMI
- Data tracking via SCADA
- Factory Automation and Process Control Systems
Installation Precautions
- Check the DN150 pipe size and flange standard
- Verify the liquid's electrical conductivity value
- Ensure that liner and electrode materials are suitable for the medium
- Check fluid pressure and temperature to ensure they do not exceed ratings
- Install with full pipe cross-section during measurement
- Avoid areas prone to air bubble accumulation
- Maintain straight pipe runs as per manufacturer's manual
- Verify grounding and electrical bonding systems
- Rewire signal cables away from power lines that may cause interference
- Check the power supply source matches the nameplate specifications
- Properly set output signals and communication settings
- Shut off power and relieve pipe pressure before removal or maintenance
Important Notes Before Purchase (Important Notes)
- The product is an Electromagnetic Flow Meter, model SG-QTLD-DN150 by SANGI.
- Pipe size DN150 or approximately 6 inches.
- For use with conductive liquids.
- Must confirm full model code before selecting liner and electrode materials.
- Select flange standards and pressure ratings that match the pipe system.
Must check the power supply and communication system of the ordered model
Check Face-to-Face distance and Dimension Drawing before installation
Should review calibration documents and warranty conditions before ordering
The SG-QTLD-DN150 standard differs from the SG-QTLD/S-DN150 Hygienic Type