SANGI SG-QTLD-DN25 Electromagnetic Flow Meter (Electromagnetic Flow Meter)
SANGI SG-QTLD-DN25 is an electromagnetic flow meter in the SG-QTLD Series designed for measuring the flow rate of electrically conductive liquids such as industrial water, wastewater, and process fluids suitable for the meter's material.
The SG-QTLD-DN25 model is designed for use with DN25 pipe systems or approximately 1 inch diameter pipes. It uses electromagnetic induction principles to measure fluid flow rates inside the pipe without requiring a rotating impeller in the flow path for measurement.
According to the SG-QTLD Series data, it supports signal transmission of 4-20mA and Pulse for industrial control systems, along with communication options such as Modbus-RS485, HART, and Profibus depending on the model code and purchased equipment.
The DN25 variant found in SCMA's list has a Compact Type structure with PTFE Liner material, Stainless Steel 316L Electrode material, and Cast Iron pipe housing. These details must be verified against the full product code before purchasing or actual use.
General Features (Features)
- SANGI flow meter
- SG-QTLD-DN25 model in SG-QTLD Series
- Type: Electromagnetic Flow Meter
- For DN25 pipe systems (1 inch)
- Meters flow rate using electromagnetic induction principles
- Suitable for liquids with electrical conductivity as per the meter's specifications
- No rotating impeller in the flow path required for measurement
- Supports display of flow rates through selected model's display unit
- Supports Analog Output 4-20mA depending on sub-model
- Supports Pulse Output depending on sub-model
- Communication option: Modbus-RS485
- Suitable for use with PLC, HMI, and compatible SCADA systems
- Fits well in water supply systems, wastewater treatment systems, and process control systems
Technical Specifications (Technical Specifications)
| Specifications |
Details |
| Brand |
SANGI |
| Model |
SG-QTLD-DN25 |
| Series |
SG-QTLD |
| Product Type |
Electromagnetic Flow Meter |
| Measurement Principle |
Electromagnetic Induction |
| Nominal Pipe Size |
DN25 (1 Inch) |
| Measured Medium |
Electrically Conductive Liquids |
| Series Pipe Size Range |
DN3-DN3000 |
| Series Flow Velocity Range |
0.1-15 m/s |
| Standard Accuracy |
±0.5% (SG-QTLD Series) |
| Optional Accuracy |
±0.3% / ±0.2% (Depending on Configuration) |
| Liquid Conductivity |
>5 µS/cm |
| Demineralized Water Conductivity |
>20 µS/cm |
| Installation Structure |
Compact Type (Referenced DN25 Configuration) |
| Maximum Working Pressure |
1.6 MPa (Referenced DN25 Configuration) |
| Liner Material |
PTFE (Referenced DN25 Configuration) |
| Electrode Material |
Stainless Steel 316L (Referenced DN25 Configuration) |
| Body Material |
Cast Iron (Referenced DN25 Configuration) |
| Flange Standard |
JIS 10K / 20K / 40K (Selection Required) |
| Power Supply |
AC 85-250 V (Referenced DN25 Configuration) |
| Analog Output |
4-20mA (Referenced DN25 Configuration) |
| Pulse Output |
Available (Referenced DN25 Configuration) |
| Communication |
Modbus (Referenced DN25 Configuration) |
| Protection Degree |
IP65 (Referenced Compact DN25 Configuration) |
| Medium Temperature |
Depends on Liner and Selected Configuration |
| Application |
Industrial Liquid Flow Measurement |
| Full Configuration Code |
Must Be Confirmed Before Ordering |
Note: SG-QTLD Series data is the general characteristics of the product group. Material PTFE, SS316L, Cast Iron, Maximum Pressure 1.6 MPa and Power Supply 85-250VAC refer to the full code SG-QTLD DN25(1")-S1-P3-L1-E1-K1-F2-D1-G1-G2-C4-F1 found in SCMA list. Full code must be confirmed before being used as the official specification of the ordered SG-QTLD-DN25
Working Principle of Electromagnetic Flow Meter
The Electromagnetic Flow Meter operates on Faraday's Law of Electromagnetic Induction by creating a magnetic field through electrically conductive liquid inside the measuring pipe.
When the liquid flows through the magnetic field, it generates a small voltage that is proportional to the flow velocity. The electrodes detect this signal and send it to the processing circuit for calculation as flow rate.
This measurement method has no mechanical turbine component in the flow path, making it suitable for fluid flow measurement systems with sufficient electrical conductivity under appropriate installation conditions.
Pipe Size DN25 (Nominal Pipe Diameter)
The SG-QTLD-DN25 uses pipe size code DN25 which is approximately 1 inch nominal diameter. Suitable for installation in piping systems that match the size and flange standard.
Before installation, check the flange size, mounting hole spacing, and Pressure Rating to match existing equipment. Do not assume all DN25 standards can be directly interchanged.
Flow Measurement Range
The general information of SG-QTLD Series specifies a flow velocity range of 0.1-15 m/s which can be used for initial selection of pipe size and measurement range.
The actual settable flow rate range and accuracy of the selected model must be verified from the Datasheet and Calibration Range settings before use, especially in applications with low flow rates or wide-ranging flow rate changes.
Measurement Accuracy
The SG-QTLD Series specifies standard measurement accuracy ±0.5% and offers options for ±0.3% or ±0.2%, depending on the order and model specification.
Must verify the measurement range, reference conditions, and calibration certificate before using the measurement results in high-precision or quality-controlled applications.
Liquid Conductivity
The electromagnetic flow meter is suitable for electrically conductive liquids. The SG-QTLD Series specifies a conductivity value greater than 5 µS/cm, while for demineralized water it must be more than 20 µS/cm.
It is not suitable for measuring non-conductive or low-conductivity liquids such as fuel oil, lubricating oil, and general hydrocarbons.
Liner Material and Electrode
The DN25 variant found in the SCMA list uses PTFE liner material and 316L Stainless Steel electrode. These materials are chosen to accommodate liquid measurement tasks based on chemical properties and appropriate temperature conditions.
PTFE is a chemically resistant material, but compatibility with actual media must be checked along with temperature, pressure, and chemical concentration before use.
The SS316L electrode material does not suit all chemicals; therefore, material compatibility should be verified before using it with corrosive liquids.
Analog Output 4-20mA Signal
The SG-QTLD Series offers a 4-20mA analog output signal option for sending flow rate values to PLCs, HMIs, Data Loggers, or other control systems that support it.
Connections should be checked for the type of output, wiring method, and scaling configuration to match the flow rate range set in the meter.
Pulse Output
The SG-QTLD meter has a pulse output option for sending pulsed signals according to specified flow volume. This is suitable for systems requiring external control devices to count cumulative flow volumes.
Before connecting, check the type of Pulse Output, voltage level, connection terminals, and Pulse Scaling values before linking with PLCs or pulse counters.
Modbus-RS485 Communication
The SG-QTLD Series supports Modbus-RS485 communication options for connecting to automatic control systems and SCADA systems. The DN25 variant found in the SCMA list specifies support for Modbus.
Before connection, check the Modbus Register Map, Slave Address, Baud Rate, Parity, and data format along with RS485 wiring methods according to the actual device manual.
Compact Display System
The reference model DN25 is of the Compact Type, where the display and signal converter are integrated with the flow measurement unit, making it convenient to read values at the installation point.
For applications with high vibration, unsuitable environmental temperatures, or difficult-to-reach installation points, consider the Remote Type if supported by the model and configuration.
Installation in Pipe System (Installation)
The meter should be installed in a position where the pipe is full of liquid across its cross-section during measurement, and avoid positions where air bubbles may accumulate or where the pipe does not flow fully, as this could affect the accuracy of the measurement.
Selecting the straight pipe lengths before and after the meter must refer to the manual of the actual ordered model, including checking grounding and electrical bonding according to the manufacturer's specifications.
Examples of Application (Applications)
- Water flow measurement systems in industrial plants
- Potable water and water supply systems
- Sewage treatment systems
- Pump and recirculation water systems
- Flow monitoring during production processes
- Liquid transfer pipelines with suitable electrical conductivity
- Flow measurement in conjunction with PLC and HMI
- Data logging and process control through SCADA
- Automation and Process Monitoring applications
Installation Precautions (Installation Precautions)
- Check the DN25 pipe size and flange standard before installation.
- Verify the type of liquid and electrical conductivity to meet specifications.
- Ensure that the Liner and Electrode materials are suitable for the medium.
- Check fluid pressure and temperature before use.
- Install the meter in a position where the pipe is full across its cross-section.
- Avoid positions with air bubble accumulation or abnormal flow.
- Allow straight pipe lengths as per manufacturer's manual.
- Verify grounding and electrical bonding according to the manual.
- Ensure power supply matches the model code before energizing.
- Rewire signal lines away from power cables and electromagnetic interference sources.
- Check Analog Output, Pulse Output, and Modbus settings before use.
- Cut off power and relieve internal pressure in the pipe before removal or maintenance.
Important Notes Before Ordering (Important Notes)
- The product is an electromagnetic flow meter SANGI model SG-QTLD-DN25.
- Pipe size DN25 (1 inch).
- Used to measure conductive liquids
- Must confirm full model number to select Compact or Remote type
- Must choose flange standard and pressure rating
- Must verify Liner and Electrode match the actual liquid
- Must select power supply voltage that matches the unit
- Check output signal and communication protocol included in sub-model
- Check mounting size and Face-to-Face distance from Dimension Drawing
- Should review calibration documentation and warranty conditions before purchase