Fiber Optic Converter SENECA S485-FO (RS485 to Fiber Optic Converter)
SENECA S485-FO Fiber Optic Converter is a communication signal converter that transforms RS485 signals into optical fiber signals for transmission and converts them back to RS485 signals when used with compatible devices on the other end. It is suitable for connecting communication systems in automation control and industrial applications.
The S485-FO supports communication through single-mode or multimode optical fibers, as well as single-loop or double-loop connection types depending on the sub-model. It features an RS485 interface with optoisolation and supports data transfer rates from 1,200 to 115,200 bps.
Transmitting data through optical fiber reduces electromagnetic interference along the communication path, making it ideal for connecting devices in PLC, HMI, Modbus RTU, and remote monitoring or control systems. However, the type of fiber, connector, and network structure must be selected to match the sub-model being used.
General Features
- Brand: SENECA
- Model: S485-FO
- Type of Product: RS485 to Fiber Optic Converter
- Converts RS485 communication signals into optical fiber signals
- Suitable for single-mode or multimode fibers depending on the sub-model
- Supports single-loop or double-loop connection types depending on the sub-model
- Data transfer rate: 1,200-115,200 bps
- Compatible with Modbus RTU and transparent data transmission
- Features an optoisolated RS485 interface
- 3-way electrical isolation system at 4 kV
- Includes status LEDs for fiber optic communication, serial communication, and device status
- Includes built-in diagnostics for device status monitoring
- Suitable for DIN rail mounting
- Designed for industrial communication and automation control systems
Technical Specifications (Technical Specifications)
| Brand | SENECA |
| Model | S485-FO |
| Product Type | RS485 to Fiber Optic Converter |
| Communication Interface | 1 x RS485, Optoisolated |
| Fiber Optic Type | Single-mode / Multimode (Depending on Version) |
| Network Configuration | Single Loop / Double Loop (Depending on Version) |
| Data Rate | 1,200-115,200 bps |
| Communication Protocol | Modbus RTU / Transparent Serial Communication |
| Power Supply | 12-35 VDC or 8-24 VAC |
| Power Consumption | 4 W at 24V (Manufacturer Reference) |
| Isolation | 4 kV, 3-way |
| Operating Temperature | -40 to +85°C |
| Dimensions (W x H x D) | 71 x 95 x 60 mm |
| Weight | 200 g |
| Enclosure Material | White PVC |
| Mounting | DIN Rail 46277 |
| Status Indicators | Fiber Optic Communication, Serial Communication, Device Status |
| Built-in Diagnostics | Yes |
| Configuration | SENECA Compositor Software (MONO Versions) / DIP Switch (MULTI Versions) |
| Single-mode Connector | LC (MONO Versions) |
| Multimode Connector | ST/ST (MULTI Versions) |
| Maximum Fiber Distance | 10 km (MONO) / 2 km (MULTI), Depending on Version |
| Maximum Converters in Series | 1,000 (Manufacturer Reference) |
| Maximum Independent Networks | 6 (Manufacturer Reference) |
| Conformity | CE |
| Applicable EMC Standards | EN 61000-6-4, EN 61000-6-2 |
How It Works
The SENECA S485-FO receives data from communication devices via the RS485 port, then converts electrical signals into light signals to transmit through fiber optic cables to a signal converter on the other end. The receiving device will then convert the light signals back into communication data for the RS485 equipment.
Fiber optic systems help reduce electromagnetic interference along the transmission path and can be applied in Modbus RTU or compatible serial communication systems by setting up Baud Rate and parameters to match those of both the originating and receiving devices.
Sub-models and Connection Types
| S485-FO-MONO-SL | Single-mode Fiber / Single Loop |
| S485-FO-MONO-DL | Single-mode Fiber / Double Loop |
| S485-FO-MULTI-SL | Multimode Fiber / Single Loop |
| S485-FO-MULTI-DL | Multimode Fiber / Double Loop |
The MONO sub-model supports single-mode fiber and uses LC connectors, with a maximum communication distance of 10 kilometers as per the manufacturer's data. The MULTI sub-model supports multimode fiber in sizes of 50/125 or 62.5/125 micrometers, using ST/ST connectors, and has a maximum communication distance of 2 kilometers, with actual distances depending on the specific sub-model, type of fiber cable, and installation conditions.
Installation and Usage
- Check the sub-model code to select the appropriate fiber type and connection configuration
- Install the device onto a DIN rail inside the control cabinet
- Connect RS485 signal wires to the control equipment according to the manufacturer's wiring diagram
- Connect the fiber optic cable to the connector that matches either the MONO or MULTI sub-models
- Supply power of 12-35 VDC or 8-24 VAC as specified in technical documentation
- Configure communication settings to match those of both RS485 originating and receiving devices
- Use SENECA Compositor for MONO sub-models, or DIP Switches for MULTI sub-models according to the manual
- Check status lights and diagnostic systems before actual use
Examples and Usage Guidelines
- Connect PLCs and RS485 devices through a fiber optic system
- Use in Modbus RTU systems for communication between measurement devices and control systems
- Apply to remote monitoring and control systems in industrial plants
Used to connect RS485 devices between separately installed control cabinets
Used in communication systems that require reducing the impact of electromagnetic interference signals
Adapted for use in Industrial Automation, Energy Monitoring and Smart Factory systems
Considerations
- S485-FO is an RS485 to Fiber Optic signal converter, not an RS232, Ethernet or CAN Converter
- The MONO or MULTI version must be selected according to the type of fiber cable and connector
- The SL or DL version must be selected according to the desired network configuration
- Maximum communication distance is 10 km or 2 km depending on sub-model and actual installation conditions
- Check the type of fiber cable, length of cable, and system loss before installation
- Verify power supply voltage and RS485 wiring diagram before powering up
- Check communication parameters and compatibility with end devices
- The code S485-FO alone cannot confirm sub-model or connector type shipped
- It is advisable to check the manual of the sub-model and actual network system before installation