Toggle Nav
My Cart 0

PLC EXPLX3V-4PT RTD Module SANGI ELECTRIC

Price on request – please contact us
Out of stock
SKU
051048
Out of stock

The price for this item is not shown online yet.

Ask for a price on LINE

SANGI ELECTRIC SCMA

PLC EXPLX3V-4PT, SANGI ELECTRIC RTD Module, PLC RTD Module, RTD Input Module, PT100 Input Module, PT100 Temperature Input Module, 4 Channel RTD Module, 4 RTD Inputs, 4 Channel PT100 Input, Industrial Temperature Input Module, Resistance Temperature Detector Module, 2-Wire RTD Input, 3-Wire RTD Input, PT100 2 Wire, PT100 3 Wire, Temperature Measurement -100 to 600C, Temperature Range -148 to 1112F, 12 Bit RTD Module, 12 Bit Resolution, Accuracy ±1% Full Scale, Input Response 15ms per 4 Channels, 24VDC RTD Module, 24VDC ±10%, Module Current 55mA, Industrial Temperature Measurement, PLC Temperature Monitoring, Industrial Sensor Input, Temperature Signal Acquisition, Industrial Automation Module, PLC I/O Expansion, Programmable Logic Controller Expansion, EXPLX3V PLC Series, Factory Automation, Machine Temperature Monitoring, Process Temperature Monitoring, SANGI ELECTRIC PLC, RTD Module, RTD Input Module, PT100 Sensor Input Module, Temperature Measurement Module, Temperature Signal Acquisition Module, PLC Expansion Module, 4 Channel Temperature Measurement Module, 4 Channel PT100 Input Module, 2-Wire RTD Module, 3-Wire RTD Module, Temperature Measurement -100 to 600C, 12 Bit Module, SANGI ELECTRIC EXPLX3V-4PT PLC Module, Industrial Temperature Measurement Module, Machine Control Module, SANGI ELECTRIC PLC Equipment, Automatic Control System, Industrial PLC System, SANGI ELECTRIC EXPLX3V-4PT Thailand

*Price does not include VAT

SCMA PLC EXPLX3V-4PT RTD Signal Receiver Module (PT100 RTD Module)

SCMA PLC EXPLX3V-4PT is an RTD (Resistance Temperature Detector) signal receiver module for PLC automatic control systems, supporting 4 channels of PT100 sensors. It is suitable for temperature measurement from multiple positions within machine tools and production processes.

The module supports both 2-Wire and 3-Wire RTD sensor connections with a temperature measurement range of -100 to +600°C or -148 to +1112°F according to SCMA General Catalog Vol.5

EXPLX3V-4PT has a signal reading resolution of 12 bit, accuracy ±1% Full Scale and input signal response time of 15 ms for 4 channels. It operates on a power supply of 24 VDC ±10%, with a current consumption of 55 mA.

It is suitable for expanding temperature measurement points in PLC systems that support it, both in Factory Automation, Machine Control and Process Monitoring applications. Before installation, check the wiring and compatibility with the PLC.

General Features (Features)

  • Brand: SANGI ELECTRIC
  • Model: PLC EXPLX3V-4PT
  • Type: RTD Module
  • Sensor Support: 4 channels of PT100 sensors
  • Used for receiving temperature signals from RTD sensors
  • Supports 2-Wire and 3-Wire sensor connections
  • Temperature measurement range -100 to +600°C
  • Temperature measurement range -148 to +1112°F
  • Input signal response time 15 ms / 4 Channels
  • Signal reading resolution 12 bit
  • Absolute accuracy ±1% Full Scale
  • Module power supply voltage 24 VDC ±10%
  • Module current consumption 55 mA
  • Suitable for temperature measurement in industrial control systems

Technical Specifications (Technical Specifications)

Specifications Details
BrandSANGI ELECTRIC
ModelPLC EXPLX3V-4PT
Product TypeRTD Module
Number of Temperature Inputs4 Channels
Supported SensorPT100
Sensor TypeRTD (Resistance Temperature Detector)
Wiring Configuration2-Wire / 3-Wire Temperature Measurement Range-100 to +600°C Temperature Range in Fahrenheit-148 to +1112°F Input Response Time15 ms / 4 Channels Input Resolution12 bit Accuracy±1% Full Scale Module Supply Voltage24 VDC ±10% Module Current Consumption55 mA Sensor Excitation CurrentNot Specified in Catalog Open Sensor DetectionNot Specified in Catalog Electrical IsolationNot Specified in Catalog DimensionsNot Specified in Catalog Operating TemperatureNot Specified in Catalog Compatible PLC ModelsTo Be Confirmed from Manufacturer Documentation Catalog ReferenceSCMA General Catalog Vol.5, D3-05

Note: The catalog confirms the number of input channels, sensor type, temperature measurement range, wiring configuration, resolution, accuracy, and response time, but does not specify details about open sensor detection, electrical isolation, or dimensions. Therefore, it is recommended to check the specific model datasheet before system design.

RTD Input 4 Channels

The PLC EXPLX3V-4PT supports 4 RTD sensors of type PT100 for receiving temperature data from various locations within machinery or production processes.

The 4-channel input allows the installation of multiple temperature sensors at different positions and feeding this data into the PLC system for processing, display, or use in control logic.

Supports PT100 Sensors

The EXPLX3V-4PT supports RTD type PT100 sensors according to catalog information, which are temperature sensors that rely on changes in platinum resistance with temperature.

Generally, a PT100 has a standard resistance value of 100 Ohm at 0°C and is commonly used for temperature measurement in industrial systems.

The selection should check the sensor type, standard resistance values, and wiring compatibility with the module.

Suitable for 2-Wire and 3-Wire Sensor Connections

The module supports RTD sensor connections of both 2-Wire and 3-Wire types as per the catalog data.

2-Wire Connection: Uses two signal wires to connect with a PT100 sensor, where the resistance of the wire may affect the reading, especially over long distances.

3-Wire Connection: This type can compensate for the impact of wire resistance under appropriate conditions by connecting according to the manufacturer's wiring diagram.

Before installation, it is necessary to check terminal numbers and channel settings to ensure accurate temperature readings.

Temperature Measurement Range -100 to +600°C

The EXPLX3V-4PT supports a temperature measurement range of -100 to +600°C or -148 to +1112°F as per the catalog data.

This measurement range is the capability of the module, and the PT100 sensors used must have appropriate temperature scale and construction for the actual environment.

The selection of a sensor should consider the probe's measuring range, sensor housing material, heat resistance, and installation characteristics as well.

Input Response Time 15 ms / 4 Channels

The catalog specifies an input signal response time of 15 ms for 4 channels, which is used to evaluate the module’s signal reading speed.

The module's Response Time value does not refer to the PT100 sensor's thermal response time, which depends on the sensor structure, installation method, and measurement environment.

Resolution 12 bit (12-bit Resolution)

The module has a signal reading resolution of 12 bits as per catalog data for converting measured data into digital values for processing in PLC systems.

A 12-bit resolution does not directly mean the accuracy of measurement, as actual measurement results depend on the module, sensor, wiring, and installation.

Accuracy ±1% Full Scale

The EXPLX3V-4PT has an accuracy of ±1% full scale according to catalog data.

To consider errors for high-precision temperature control applications, one should review the datasheet and account for PT100 sensor inaccuracies as well as signal wire impact.

24 VDC ±10% Power Supply System

The module uses a 24 VDC ±10% power supply and has a working current of 55 mA, according to the catalog data.

The design of the power supply system should consider the electrical load in conjunction with other modules within the PLC system and verify the power supply wiring method as per the manufacturer's manual.

Compatibility with PLC Systems

EXPLX3V-4PT is an RTD module for expanding temperature measurement points for PLC systems that support it. Compatibility with CPU and expansion module requirements must be verified before installation.

The sensor configuration, wiring, and temperature display in the control program should be checked to ensure system requirements are met.

Applications

  • Temperature monitoring in industrial machinery
  • Sensor PT100 signal reception systems
  • Multilocation temperature measurement systems
  • Process production temperature checking systems
  • Equipment or machine component temperature measurement systems
  • PLC Temperature Monitoring Systems
  • Factory Automation and Machine Control Systems
  • Design and development of industrial temperature monitoring systems

Selecting PLC EXPLX3V-4PT Guidelines

  • Check the number of required temperature measurement points
  • Verify that the sensor is PT100 type
  • Check 2-Wire or 3-Wire wiring configuration
  • Check the desired temperature range to be measured
  • Consider a resolution of 12 bit
  • Consider accuracy ±1% Full Scale
  • Verify input response time at 15 ms / 4 Channels
  • Verify the power supply system of 24 VDC ±10%
  • Check compatibility with main PLC
  • Review Wiring Diagram and sensor terminal positions

Installation Precautions

  • Use PT100 sensors that meet module specifications
  • Verify 2-Wire or 3-Wire RTD terminals according to the manual
  • Check wire resistance which may affect measurement values
  • Select cable type and installation to prevent interference as appropriate
  • Do not connect external power supply to the RTD sensor terminal without manufacturer approval
  • Verify power source meets 24 VDC ±10% specifications
  • Do not plug or unplug modules while powered, unless specified by the manufacturer's manual
  • Test temperature readings on all channels before actual use
  • Check measurement values against reference equipment when necessary
  • Important Notes (Important Notes)

    • Product is SANGI ELECTRIC RTD Module model PLC EXPLX3V-4PT
    • SUPPORTS PT100 sensors, 4 channels
    • SUPPORTS 2-Wire and 3-Wire wiring methods
    • MESURING RANGE -100 to +600°C
    • INPUT RESPONSE TIME 15 ms / 4 Channels
    • PRECISION 12 bit
    • ACCURACY ±1% Full Scale
    • POWER SUPPLY 24 VDC ±10%, CURRENT 55 mA
    • DON'T USE the Thermocouple SPEC of model EXPLX3V-4TC as a substitute
    • CHECK compatibility with PLC and other devices before ordering
    More Information
    Delivery Days3 days
    Write Your Own Review
    You're reviewing:PLC EXPLX3V-4PT RTD Module SANGI ELECTRIC
    Cookie settings
    🤖 AI Assistant
    Ask about products, specs and replacement models
    Hello 👋 Ask us anything — find products, compare specs, or troubleshoot.