SCMA PLC EXPLX3V-4PT is an RTD (Resistance Temperature Detector) signal receiver module for PLC automatic control systems, supporting 4 channels of PT100 sensors. It is suitable for temperature measurement from multiple positions within machine tools and production processes.
The module supports both 2-Wire and 3-Wire RTD sensor connections with a temperature measurement range of -100 to +600°C or -148 to +1112°F according to SCMA General Catalog Vol.5
EXPLX3V-4PT has a signal reading resolution of 12 bit, accuracy ±1% Full Scale and input signal response time of 15 ms for 4 channels. It operates on a power supply of 24 VDC ±10%, with a current consumption of 55 mA.
It is suitable for expanding temperature measurement points in PLC systems that support it, both in Factory Automation, Machine Control and Process Monitoring applications. Before installation, check the wiring and compatibility with the PLC.
General Features (Features)
- Brand: SANGI ELECTRIC
- Model: PLC EXPLX3V-4PT
- Type: RTD Module
- Sensor Support: 4 channels of PT100 sensors
- Used for receiving temperature signals from RTD sensors
- Supports 2-Wire and 3-Wire sensor connections
- Temperature measurement range -100 to +600°C
- Temperature measurement range -148 to +1112°F
- Input signal response time 15 ms / 4 Channels
- Signal reading resolution 12 bit
- Absolute accuracy ±1% Full Scale
- Module power supply voltage 24 VDC ±10%
- Module current consumption 55 mA
- Suitable for temperature measurement in industrial control systems
Technical Specifications (Technical Specifications)
| Specifications |
Details |
| Brand | SANGI ELECTRIC |
| Model | PLC EXPLX3V-4PT |
| Product Type | RTD Module |
| Number of Temperature Inputs | 4 Channels |
| Supported Sensor | PT100 |
| Sensor Type | RTD (Resistance Temperature Detector) |
| Wiring Configuration | 2-Wire / 3-Wire |
| Temperature Measurement Range | -100 to +600°C |
| Temperature Range in Fahrenheit | -148 to +1112°F |
| Input Response Time | 15 ms / 4 Channels |
| Input Resolution | 12 bit |
| Accuracy | ±1% Full Scale |
| Module Supply Voltage | 24 VDC ±10% |
| Module Current Consumption | 55 mA |
| Sensor Excitation Current | Not Specified in Catalog |
| Open Sensor Detection | Not Specified in Catalog |
| Electrical Isolation | Not Specified in Catalog |
| Dimensions | Not Specified in Catalog |
| Operating Temperature | Not Specified in Catalog |
| Compatible PLC Models | To Be Confirmed from Manufacturer Documentation |
| Catalog Reference | SCMA General Catalog Vol.5, D3-05 |
Note: The catalog confirms the number of input channels, sensor type, temperature measurement range, wiring configuration, resolution, accuracy, and response time, but does not specify details about open sensor detection, electrical isolation, or dimensions. Therefore, it is recommended to check the specific model datasheet before system design.
RTD Input 4 Channels
The PLC EXPLX3V-4PT supports 4 RTD sensors of type PT100 for receiving temperature data from various locations within machinery or production processes.
The 4-channel input allows the installation of multiple temperature sensors at different positions and feeding this data into the PLC system for processing, display, or use in control logic.
Supports PT100 Sensors
The EXPLX3V-4PT supports RTD type PT100 sensors according to catalog information, which are temperature sensors that rely on changes in platinum resistance with temperature.
Generally, a PT100 has a standard resistance value of 100 Ohm at 0°C and is commonly used for temperature measurement in industrial systems.
The selection should check the sensor type, standard resistance values, and wiring compatibility with the module.
Suitable for 2-Wire and 3-Wire Sensor Connections
The module supports RTD sensor connections of both 2-Wire and 3-Wire types as per the catalog data.
2-Wire Connection: Uses two signal wires to connect with a PT100 sensor, where the resistance of the wire may affect the reading, especially over long distances.
3-Wire Connection: This type can compensate for the impact of wire resistance under appropriate conditions by connecting according to the manufacturer's wiring diagram.
Before installation, it is necessary to check terminal numbers and channel settings to ensure accurate temperature readings.
Temperature Measurement Range -100 to +600°C
The EXPLX3V-4PT supports a temperature measurement range of -100 to +600°C or -148 to +1112°F as per the catalog data.
This measurement range is the capability of the module, and the PT100 sensors used must have appropriate temperature scale and construction for the actual environment.
The selection of a sensor should consider the probe's measuring range, sensor housing material, heat resistance, and installation characteristics as well.
Input Response Time 15 ms / 4 Channels
The catalog specifies an input signal response time of 15 ms for 4 channels, which is used to evaluate the module’s signal reading speed.
The module's Response Time value does not refer to the PT100 sensor's thermal response time, which depends on the sensor structure, installation method, and measurement environment.
Resolution 12 bit (12-bit Resolution)
The module has a signal reading resolution of 12 bits as per catalog data for converting measured data into digital values for processing in PLC systems.
A 12-bit resolution does not directly mean the accuracy of measurement, as actual measurement results depend on the module, sensor, wiring, and installation.
Accuracy ±1% Full Scale
The EXPLX3V-4PT has an accuracy of ±1% full scale according to catalog data.
To consider errors for high-precision temperature control applications, one should review the datasheet and account for PT100 sensor inaccuracies as well as signal wire impact.
24 VDC ±10% Power Supply System
The module uses a 24 VDC ±10% power supply and has a working current of 55 mA, according to the catalog data.
The design of the power supply system should consider the electrical load in conjunction with other modules within the PLC system and verify the power supply wiring method as per the manufacturer's manual.
Compatibility with PLC Systems
EXPLX3V-4PT is an RTD module for expanding temperature measurement points for PLC systems that support it. Compatibility with CPU and expansion module requirements must be verified before installation.
The sensor configuration, wiring, and temperature display in the control program should be checked to ensure system requirements are met.
Applications
- Temperature monitoring in industrial machinery
- Sensor PT100 signal reception systems
- Multilocation temperature measurement systems
- Process production temperature checking systems
- Equipment or machine component temperature measurement systems
- PLC Temperature Monitoring Systems
- Factory Automation and Machine Control Systems
- Design and development of industrial temperature monitoring systems
Selecting PLC EXPLX3V-4PT Guidelines
- Check the number of required temperature measurement points
- Verify that the sensor is PT100 type
- Check 2-Wire or 3-Wire wiring configuration
- Check the desired temperature range to be measured
- Consider a resolution of 12 bit
- Consider accuracy ±1% Full Scale
- Verify input response time at 15 ms / 4 Channels
- Verify the power supply system of 24 VDC ±10%
- Check compatibility with main PLC
- Review Wiring Diagram and sensor terminal positions
Installation Precautions
- Use PT100 sensors that meet module specifications
- Verify 2-Wire or 3-Wire RTD terminals according to the manual
- Check wire resistance which may affect measurement values
- Select cable type and installation to prevent interference as appropriate
- Do not connect external power supply to the RTD sensor terminal without manufacturer approval
- Verify power source meets 24 VDC ±10% specifications
- Do not plug or unplug modules while powered, unless specified by the manufacturer's manual
- Test temperature readings on all channels before actual use
Check measurement values against reference equipment when necessary
Important Notes (Important Notes)
- Product is SANGI ELECTRIC RTD Module model PLC EXPLX3V-4PT
- SUPPORTS PT100 sensors, 4 channels
- SUPPORTS 2-Wire and 3-Wire wiring methods
- MESURING RANGE -100 to +600°C
- INPUT RESPONSE TIME 15 ms / 4 Channels
- PRECISION 12 bit
- ACCURACY ±1% Full Scale
- POWER SUPPLY 24 VDC ±10%, CURRENT 55 mA
- DON'T USE the Thermocouple SPEC of model EXPLX3V-4TC as a substitute