SANGI ELECTRIC PLC EXPLX3V-4AD (Analog Input Module)
SANGI ELECTRIC PLC EXPLX3V-4AD is an analog input expansion module for PLC control systems, supporting 4 channels of analog input signals. It can accept standard voltage signals ranging from -10 V to +10 V and current signals in the range of 4-20 mA.
The module is suitable for connecting measuring and signaling devices in industrial systems such as Pressure Transmitter, Flow Transmitter, and Temperature Transmitter that have outputs matching the supported signal ranges. This allows data to be fed into the PLC system for processing, monitoring, and controlling machinery.
The device has a 12-bit resolution for signal conversion and supports an input response time of 15 ms/channel in Normal Speed mode and 6 ms/channel in High Speed mode as per the catalog specifications. The accuracy is ±1% for both types of signals according to the catalog.
The module operates on a power supply voltage of 24 VDC ±10%, with a current consumption of 55 mA, as specified in the catalog. It is suitable for expanding the analog input channels of compatible PLC systems.
Features
- Brand: SANGI ELECTRIC
- Model: PLC EXPLX3V-4AD
- Type: Analog Input Module
- Analog Inputs Supported: 4 Channels
- Voltage Signal Range: -10 V to +10 V
- Current Signal Range: 4-20 mA
- Signal Reading Resolution: 12 bit
- Normal Speed Mode Response Time: 15 ms/channel
- High Speed Mode Response Time: 6 ms/channel
- Absolute Accuracy ±1% as per catalog
- Module Power Supply Voltage: 24 VDC ±10%
- Module Current Consumption: 55 mA
- Suitable for signals from Transmitters and industrial measuring devices
- Used to expand Analog Input for compatible PLC systems
Technical Specifications
| Specifications |
Details |
| Brand | SANGI ELECTRIC |
| Model | PLC EXPLX3V-4AD |
| Product Type | Analog Input Module |
| Number of Analog Inputs | 4 Channels |
| Voltage Input Range | -10 V to +10 V |
| Current Input Range | 4-20 mA |
| Normal Speed | 15 ms/channel |
| High Speed | 6 ms/channel |
| Input Resolution | 12 bit |
| Accuracy - Voltage Input | ±1% (-10 V to +10 V) |
| Accuracy - Current Input | ±1% (4-20 mA) |
| Module Supply Voltage | 24 VDC ±10% |
| Module Current Consumption | 55 mA |
| Input Impedance | Not Specified in Catalog |
| Electrical Isolation | Not Specified in Catalog |
| Dimensions | Not Specified in Catalog |
| Operating Temperature | Not Specified in Catalog |
| Compatible PLC Models | To Be Confirmed from Manufacturer Documentation |
| Catalog Reference | SCMA General Catalog Vol.5, D3-05 |
Note: The catalog confirms the number of input channels, signal range for voltage and current, resolution, response time, accuracy, and module power supply information, but does not specify Input Impedance, isolation details, dimensions, or supported PLC models completely. Therefore, it is recommended to check the specific model datasheet before system design.
4 Analog Inputs
The SCMA EXPLX3V-4AD supports 4 analog signal inputs for connecting with measuring and signaling devices that have outputs compatible with standard signal ranges supported by the module.
This can be applied to receive data from multiple measurement points in a production process, but each channel configuration must be checked according to the manufacturer's manual.
Supports Voltage Signal -10 V to +10 V
The module supports analog voltage signals within the range of -10 V to +10 V as per catalog information. It is suitable for connecting devices that send bipolar voltage signals.
Before use, it is necessary to check signal terminals, reference voltages, and maximum acceptable voltage levels from the manufacturer's wiring diagram.
Supports Current Signal 4-20 mA
EXPLX3V-4AD supports the standard analog current signal of 4-20 mA, commonly used in industrial process measurement and control systems.
It can be applied to devices with a 4-20 mA output such as Pressure Transmitter, Flow Transmitter or Temperature Transmitter that are electrically compatible.
The selection must check whether the source device is Active or Passive type, as well as the power supply configuration of the Current Loop before connecting to the module.
Normal Speed and High Speed Modes
| Operating Mode |
Response Time |
| Normal Speed | 15 ms/channel |
| High Speed | 6 ms/channel |
The module has two response time modes for input consideration as per the catalog data, which can be selected based on signal characteristics and measurement process capabilities of the system.
Further details about mode configuration and impact on accuracy or signal filtering should be reviewed from the manufacturer's manual.
12-bit Resolution
The EXPLX3V-4AD has a 12-bit resolution for analog signal conversion, used to convert signals from external devices into digital values for processing in PLC systems.
A 12-bit resolution does not imply measurement accuracy as actual accuracy still depends on the circuitry of the signal converter, installation conditions and characteristics of connected measuring equipment.
Accuracy ±1%
The catalog specifies an accuracy of ±1% for signals ranging from -10 V to +10 V voltage and 4-20 mA current.
Detailed calculation basis and testing conditions for accuracy must be reviewed from the Datasheet before use in applications with specific precision requirements.
Power Supply 24 VDC ±10%
The module uses a power supply of 24 VDC ±10% and specifies an operating current of 55 mA for control cabinet power system design.
Sufficient power allowance should be considered for other devices in the system, along with checking the power supply configuration and circuit protection requirements as per the manufacturer's manual.
Usage with PLC Systems
The EXPLX3V-4AD is an Analog Input module to expand the number of signal channels supported by PLC systems. Before installation, compatibility must be checked for the main CPU model, maximum connected modules and channel configuration methods.
The name EXPLX3V Series should not be used to confirm compatibility with all CPU models without a manual.
Applications
- Pressure Transmitter Signal Reception System
- Flow Transmitter Signal Reception System
- Temperature Transmitter Signal Reception System
- -10 V to +10 V Voltage Signal Measurement System
- 4-20 mA Current Signal Measurement System
- Monitoring and Process Control Systems
- Analog Input Expansion for PLCs
- Factory Automation and Machine Control Systems
- Control and Monitoring System Development in Industries
Selecting the EXPLX3V-4AD PLC
- Check the number of Analog Input channels needed
- Verify the type of signal from the source device
- Confirm the signal range -10 V to +10 V or 4-20 mA
- Consider response time 15 ms/channel or 6 ms/channel
- Evaluate 12 bit resolution suitable for use
- Check accuracy condition ±1%
- Determine Active or Passive current circuit configuration
- Verify power supply 24 VDC ±10%
- Confirm compatibility with the main PLC
- Review Wiring Diagram and signal channel setting procedures
Installation Precautions
- Check Voltage or Current signal mode before wiring
- Avoid exceeding Analog Input channel limits
- Verify signal terminals and reference points according to the Wiring Diagram
- Use power supply with appropriate ratings for the module
- Follow manufacturer's specifications for Shield and Ground wiring
- Separate analog signals from noisy power lines as necessary
- Check signal range and Scaling settings in PLC program
- Avoid inserting or removing modules while powered unless specified by the manual
- Test all 4 channels before putting the system into actual use
Important Notes Before Purchase
- The product is a SANGI ELECTRIC Analog Input Module model PLC EXPLX3V-4AD
- Suitable for up to 4 Analog Input channels
- Supports -10 V to +10 V voltage signals
- Supports 4-20 mA current signals
- Has response time of 15 ms/channel and 6 ms/channel depending on mode
- Offers 12 bit resolution
Catalog specifies accuracy ±1%
Operates on 24 VDC ±10% power supply, current 55 mA
This is not the Analog Output Module model EXPLX3V-4DA
Must check compatibility with PLC and accessories before ordering