KYORITSU KEW 4506 Intelligent Socket Tester is an intelligent socket tester for checking the correctness of electrical wiring connections within a socket. It can check Line (L), Neutral (N), and Earth (E) wires, as well as detect wire swapping, missing wires, and abnormal voltage conditions.
The device is designed for easy use. Simply connect it to the socket via an appropriate test lead and press the test button to quickly check the wiring condition. It supports AC voltage measurement and measurement of the N-E loop resistance, suitable for installation and inspection of electrical systems in buildings and industrial facilities.
Display: Displays PASS / FAIL and wiring conditions
Power Supply: LR6 (AA) 1.5V, 2 pcs
Dimensions: 212 x 56 x 39 mm
Weight: Approximately 250 g (including batteries)
Protection Rating: IP40
Socket Wiring Test
The device supports testing of 2 Pole and 3 Pole sockets, and can display the status of correct or incorrect connections as follows:
PASS: The wiring connection is in a condition determined by the tester as correct
L-N Reverse: Line and Neutral wires are swapped
L-E Reverse: Line and Earth wires are swapped
N-E Reverse: Neutral and Earth wires are swapped
E Not Connected: No connection to the Earth wire is detected
N Not Connected: No Neutral wire connection detected
N-E Unjudgeable: The device cannot clearly identify the condition between Neutral and Earth
Abnormal Voltage: Abnormal voltage detected
Note: The error detection format depends on the type of socket. Some statuses support only 3 Pole testing.
AC Voltage Measurement
Measurement Position: Line-Neutral (L-N)
Measurement Range: 80-290V RMS
Frequency: 50/60Hz
Accuracy: ±(2%rdg+4dgt)
Alert: An alert signal is triggered when the detected voltage is 253V or higher
Neutral-Earth (N-E) Loop Resistance Measurement
Item
200Ω Range
2000Ω Range
Measurement Range
0.0-199.9Ω
200-1999Ω
Test Current
5mA (5.3Hz)
1mA (5.3Hz)
Accuracy
±(3%rdg+5dgt)
±(3%rdg+5dgt)
Usage Modes
Quickly check the wiring of electrical sockets
Check the swapping positions of Line, Neutral, and Earth
Supports TT and TN-S grounding system testing when used with KEW 8343 device under manufacturer conditions
Use low test current for Loop Resistance measurement to reduce the chance of RCD tripping during testing
Check socket voltage to help assess power supply conditions
Operating Environment
Operating Temperature: -10 to 50°C
Operating Humidity: Not exceeding 85% RH without condensation
Storage Temperature: -20 to 60°C
Storage Humidity: Not exceeding 85% RH without condensation
Safety Standards
IEC 61010-1
IEC 61010-2-030
CAT II 300V
Pollution Degree 2
IEC 60529 IP40
Standard Equipment
Test lead with IEC connector
Carrying case, model 9161
2 LR6 (AA) batteries
Instruction manual
Optional Accessories
KEW 8343: Signal Source for Intelligent Socket Tester for use with KEW 4506 according to the specified test method
Examples and Usage Guidelines
Inspect electrical wiring of sockets inside buildings
Check for Line and Neutral wire swapping
Check grounding wire connections in sockets
Check AC voltage at usage points
Check N-E circuit resistance
Check sockets after new electrical system installation
Inspect and maintain electrical systems in offices and industrial factories
Limitations and Considerations
The device is designed for checking sockets within the specified voltage range and is not suitable for circuits exceeding the rated voltage
The wiring check function supports different types of sockets and abnormal conditions according to 2 Pole or 3 Pole configurations
Use with TT and TN-S grounding systems may require the optional accessory KEW 8343 in some cases
Measurement of N-E Loop Resistance is not a direct measurement of earth resistance
A PASS result does not guarantee that the electrical system is fully safe under all conditions
The device does not directly test RCD trip current and trip time functions
Ensure that the plug type and test lead are compatible with the socket to be tested before ordering