KEPLER KCTM-36 V Split Core Current Transformer
KEPLER KCTM-36 V Split Core Current Transformer is a detachable core (Split Core CT) current transformer for measuring alternating current in electrical systems. It has a primary rated current of 500A and an output voltage rating of 333mV AC, suitable for use with electricity metering devices and current measurement equipment that support a 333mV AC input.
The split core design allows the transformer's core to be opened and closed to install around electrical conductors without needing to disconnect existing wire ends from their connections. This increases installation convenience for current measurement systems, though power sources should be disconnected and safety measures followed before installation.
KEPLER KCTM-36 V belongs to the KCTM-36V Series, which is a 333mV AC output voltage type of current transformer. This differs from the KCTM-36 model with a 5A output current, so appropriate signal receiving equipment and setting current ratings must match the CT type.
General Features
- Brand: KEPLER
- Product Model: KCTM-36 V
- Product Type: Split Core Current Transformer
- Detachable core design allows opening of the core for installation around electrical conductors
- Rated primary current: 500A AC
- Rated output voltage: 333mV AC
- Precision: Class 0.5 according to series data
- Supports frequency range: 50-60Hz
- Housing made of PC / UL94-V0 material
- Suitable for current measurement and electricity consumption monitoring systems
Technical Specifications (Technical Specifications)
| Brand | KEPLER |
| Model | KCTM-36 V |
| Product Series | KCTM-36V Series |
| Product Type | Split Core Current Transformer |
| Rated Primary Current | 500A AC |
| Rated Output | 333mV AC |
| Accuracy Class | Class 0.5 (Series Reference) |
| Accuracy Range | 20% to 120% of Rated Current (Series Reference) |
| Frequency | 50-60Hz |
| Phase Angle | Less than 2 degrees at 50% of rated current (Series Reference) |
| Insulation Voltage | 600VAC (Series Reference) |
| Maximum Primary Voltage | 5000VAC, Insulated Conductor (Series Reference) |
| Dielectric Strength | 2.5kV / 1mA / 1min (Series Reference) |
| Operating Temperature | -15 to +60°C |
| Operating Humidity | Less than 85% RH |
| Case Material | PC / UL94-V0 |
| Bobbin Material | PBT |
| Core Material | Permalloy |
| Internal Structure | Epoxy |
| Lead Wire | UL1015, Twisted Pair, 22 AWG (Series Reference) |
| Compatible Measurement Input | 333mV AC CT Input |
Operating Principle
A split core current transformer operates based on the principle of electromagnetic induction. When alternating current flows through a conductor within the CT core, it generates a magnetic field that induces an electrical signal in the secondary winding.
The KEPLER KCTM-36 V with a rating of 500A/333mV is designed to provide an output voltage of 333mV AC when the primary current equals 500A AC. The output signal varies in proportion to the measured current, under conditions specified by the manufacturer.
The 333mV AC output voltage can be used with measurement devices that support CT output voltage. It is necessary to set the CT rating in the receiving device to match 500A/333mV for accurate current readings.
Installation and Usage
- Select the alternating current conductor where you want to measure the current.
- Cut off power supply and ensure there is no voltage before installation.
- Open the split core and install it around a single wire of the circuit that needs measurement.
- Close the CT core completely according to the locking mechanism of the device.
- Connect the signal wires to a meter supporting 333mV AC CT input.
- Set the CT rating in the measuring device to match 500A/333mV.
Check the installation direction and signal polarity from the manufacturer's documentation
Ensure that the CT core channel size is appropriate for the wire or bus bar size
Examples and Usage Guidelines
- Measure electrical current in control panels and distribution boards
- Use with Energy Monitoring systems supporting 333mV CT input
- Monitor load currents of machinery and industrial equipment
- Apply in building energy consumption monitoring systems
- Use for current measurement installations requiring open-CT installation
Considerations
- This model is a 333mV AC output CT, not a 5A output CT
- Meters or measuring devices supporting 333mV AC CT input must be used in conjunction with it
- Check the current rating and measurement range to match actual usage requirements
- For general load current measurements, wrap the CT around a single conductor wire only, not around phase and neutral wires together
- Verify the CT core channel size and installation space before selecting for use
- Configure CT Rating settings and signal polarity prior to operation
- Avoid using 333mV CT as a direct replacement for 5A CT
- Some technical data references KCTM-36V Series; check specific model documentation before installation
- Installation in electrical systems must be carried out by qualified personnel following electrical safety measures