KEPLER KCTM-36 V Split Core Current Transformer
KEPLER KCTM-36 V Split Core Current Transformer is a detachable core (Split Core CT) current transformer for measuring alternating current in electrical systems. It has a primary rated current of 400A and an output of 333mV AC at the rated current, suitable for use with meters and other current measurement devices that support a 333mV AC CT input.
The device is designed to allow opening and closing of the transformer core, making it possible to install around the desired electrical conductor without needing to disconnect existing connections. However, power sources should be disconnected and safety measures followed before installation.
Model KCTM-36 V belongs to the KEPLER KCTM-36V Series and provides an output signal of 333mV AC, differing from transformers with a 5A output. Therefore, it is necessary to select compatible measuring equipment.
General Features
- Brand: KEPLER
- Model: KCTM-36 V
- Type of Product: Split Core Current Transformer
- Detachable core current transformer, can open the core to fit around conductors
- Rated primary current: 400A AC
- Rated output voltage: 333mV AC
- Precision: Class 0.5 according to series data
- Supports frequency range: 50-60Hz
- Housing made of PC / UL94-V0 material
- Suitable for current measurement systems and energy monitoring
Technical Specifications (Technical Specifications)
| Brand | KEPLER |
| Model | KCTM-36 V |
| Product Series | KCTM-36V Series |
| Product Type | Split Core Current Transformer |
| Rated Primary Current | 400A AC |
| Rated Output | 333mV AC |
| Accuracy Class | Class 0.5 (Series Reference) |
| Frequency | 50-60Hz |
| Phase Angle | Less than 2 degrees at 50% of rated current (Series Reference) |
| Insulation Voltage | 600VAC (Series Reference) |
| Maximum Primary Voltage | 5000VAC, Insulated Conductor (Series Reference) |
| Dielectric Strength | 2.5kV / 1mA / 1min (Series Reference) |
| Operating Temperature | -15 to +60°C |
| Operating Humidity | Less than 85% RH |
| Case Material | PC / UL94-V0 |
| Bobbin Material | PBT |
| Core Material | Permalloy |
| Internal Structure | Epoxy |
| Lead Wire | UL1015, Twisted Pair, 22 AWG (Series Reference) |
| Compatible Measurement Input | 333mV AC CT Input |
Principle of Operation
The Split Core Current Transformer operates based on the principle of electromagnetic induction. When alternating current flows through the conductor inside the CT core, a magnetic field is generated and induces an electrical signal in the secondary winding.
For model KCTM-36 V with a rating of 400A/333mV, the device is designed to have an output voltage rating of 333mV AC when there is a primary current of 400A AC. The output voltage changes in proportion to the measured current under the operating conditions specified by the manufacturer.
The 333mV AC output signal can be used with meters or measuring devices that support CT output voltage, provided that the CT ratio is set correctly at 400A/333mV for accurate current measurement.
Installation and Usage
- Select the alternating conductor where you want to measure the current.
- Disconnect power supply and ensure there is no voltage before installation.
- Open the Split Core and install it around a single wire of the circuit that needs to be measured.
- Cover the CT core completely according to the locking mechanism of the device.
- Connect the signal wires to a meter supporting 333mV AC CT input.
- Set the CT Ratio or CT Rating in the measuring device to match 400A/333mV.
- Check the installation direction and polarity according to the manufacturer's documentation.
Examples and Usage Guidelines
- Measure electrical current in control panels and power distribution cabinets
- Works with Energy Monitoring systems supporting 333mV CT input
- Measures load currents of machinery and industrial electrical equipment
- Applied to building energy consumption monitoring systems
- Used for current measurement requiring open-CT installation
Considerations
- This model is a 333mV AC output CT, not a 5A output CT
- Meters or measuring devices supporting 333mV AC input must be used in conjunction with it
- Check the current rating and measurement range to match actual usage requirements
- Verify the CT core size fits the wire gauge or bus bar before installation
- For general load current measurements, wrap the CT around a single conductor only, not around phase and neutral wires together
- Ensure CT Ratio settings and signal polarity are correctly configured before use
- Some technical data references KCTM-36V Series; check specific model documentation prior to installation
- Installation in electrical systems must be carried out by qualified personnel following electrical safety measures