KEPLER KCTM-24 V Split Core Current Transformer
KEPLER KCTM-24 V Split Core Current Transformer is a detachable core (Split Core CT) current transformer designed for measuring alternating current in electrical systems. It has a primary rated current of 300A and an output of 333mV AC at the rated current, suitable for use with measurement devices or meters that support a 333mV AC CT input.
The device is designed to allow opening and closing of the transformer core, enabling installation around electrical conductors without needing to disconnect existing connections. However, installation must follow appropriate electrical safety procedures.
Model KCTM-24 V belongs to the KEPLER KCTM-24V Series with an output voltage of 333mV AC, differing from transformers that have a 5A output, thus requiring selection and use with compatible signal receiving equipment.
General Features
- Brand: KEPLER
- Model: KCTM-24 V
- Type of Product: Split Core Current Transformer
- Detachable core current transformer, can open the core for installation around conductors.
- Rated primary current: 300A AC
- Rated output voltage: 333mV AC
- Precision: Class 0.5 as per series catalog data
- Supports frequency range: 50-60Hz
- Housing made of PC / UL94-V0 material
- Suitable for current measurement and energy monitoring systems.
Technical Specifications (Technical Specifications)
| Brand | KEPLER |
| Model | KCTM-24 V |
| Product Series | KCTM-24V Series |
| Product Type | Split Core Current Transformer |
| Rated Primary Current | 300A AC |
| Rated Output | 333mV AC |
| Accuracy Class | Class 0.5 (Series Reference) |
| Frequency | 50-60Hz |
| Phase Angle | Less than 2 degrees at 50% of rated current (Series Reference) |
| Insulation Voltage | 600VAC (Series Reference) |
| Maximum Primary Voltage | 5000VAC, Insulated Conductor (Series Reference) |
| Dielectric Strength | 2.5kV / 1mA / 1min (Series Reference) |
| Operating Temperature | -15 to +60°C |
| Operating Humidity | Less than 85% RH |
| Case Material | PC / UL94-V0 |
| Bobbin Material | PBT |
| Core Material | Permalloy |
| Internal Structure | Epoxy |
| Lead Wire | UL1015, Twisted Pair, 22 AWG (Series Reference) |
| Compatible Measurement Input | 333mV AC CT Input |
How It Works
A split core current transformer operates based on the principle of electromagnetic induction. When alternating current flows through a conductor within the CT core, it generates a magnetic field that induces an electrical signal in the secondary winding.
The KCTM-24 V model with a rating of 300A/333mV is designed to have an output voltage rating of 333mV AC when there is a primary current of 300A AC. The output voltage changes proportionally to the measured current, under conditions specified by the manufacturer.
The 333mV AC output signal can be used with meters or measurement devices that have an input for CTs rated at 333mV. It is necessary to set the CT ratio to match 300A/333mV in order for the system to accurately display current.
Installation and Usage
- Select the alternating conductor where you want to measure the current.
- Cut off power supply and ensure there is no voltage before installation.
- Open the split core and install it around a single wire of the circuit that needs to be measured.
- Close the CT core completely according to the locking mechanism of the device.
- Connect the signal wires to a meter that supports 333mV AC CT input.
- Set the CT Ratio or CT Rating in the measuring device to match 300A/333mV.
- Check the installation direction and polarity from the manufacturer's documentation.
Examples and Usage Guidelines
- Measure electrical current in control panels and power distribution cabinets
- Works with Energy Monitoring systems supporting 333mV CT input
- Measures load currents of machinery and industrial electrical equipment
- Adaptable for building energy consumption monitoring systems
- Used with current measurement systems requiring open-CT installation
Considerations
- This model is a 333mV AC output CT, not a 5A output CT
- Meters or measuring devices supporting 333mV AC input must be used in conjunction
- Check the current rating and measurement range to match actual usage requirements
- Verify that the CT core size is appropriate for the wire or busbar size
- For general load current measurements, wrap the CT around a single conductor only, not around phase and neutral wires together
- Ensure proper CT Ratio settings and signal polarity before use
- Some technical data references KCTM-24V Series; installation documentation should be reviewed for specific model details
- Installation in electrical systems must be performed by qualified personnel following electrical safety measures