KEPLER KCTM-24 V Split Core Current Transformer with Rating 250A/333mV
The KEPLER KCTM-24 V Split Core Current Transformer is a current transformer designed for measuring alternating current in electrical systems, featuring a primary current rating of 250A and an output voltage of 333mV AC at rated current. It is suitable for use with measurement devices or meters that support CT input signals of 333mV AC.
The device is designed to allow the transformer core to be opened and closed, enabling installation around electrical conductors without needing to disconnect them from their original connection points, provided appropriate electrical safety measures are followed before installation.
Model KCTM-24 V belongs to KEPLER's KCTM-24V Series and provides an output signal of 333mV AC voltage, which differs from the standard 5A output current transformers. Therefore, it is necessary to select compatible receiving equipment that supports this type of output.
General Features
- Brand: KEPLER
- Model: KCTM-24 V
- Type: Split Core Current Transformer
- Split core design allows the transformer to be opened for installation around conductors
- Rated primary current: 250A AC
- Rated output voltage: 333mV AC
- Precision: Class 0.5 as per series catalog data
- Supports frequency range: 50-60Hz
- Housing made of PC / UL94-V0 material
- Suitable for current measurement and energy monitoring systems
Technical Specifications (Technical Specifications)
| Brand | KEPLER |
| Model | KCTM-24 V |
| Product Series | KCTM-24V Series |
| Product Type | Split Core Current Transformer |
| Rated Primary Current | 250A AC |
| Rated Output | 333mV AC |
| Accuracy Class | Class 0.5 (Series Reference) |
| Frequency | 50-60Hz |
| Phase Angle | Less than 2 degrees at 50% of rated current (Series Reference) |
| Insulation Voltage | 600VAC (Series Reference) |
| Maximum Primary Voltage | 5000VAC, Insulated Conductor (Series Reference) |
| Dielectric Strength | 2.5kV / 1mA / 1min (Series Reference) |
| Operating Temperature | -15 to +60°C |
| Operating Humidity | Less than 85% RH |
| Case Material | PC / UL94-V0 |
| Bobbin Material | PBT |
| Core Material | Permalloy |
| Internal Structure | Epoxy |
| Lead Wire | UL1015, Twisted Pair, 22 AWG (Series Reference) |
| Compatible Measurement Input | 333mV AC CT Input |
Functionality
The Split Core Current Transformer operates based on the principle of electromagnetic induction. When alternating current flows through a conductor within the CT core, it generates a magnetic field that induces an electrical signal in the secondary winding.
For model KCTM-24 V with a rating of 250A/333mV, the device is designed to have an output voltage rating of 333mV AC when there is a primary current of 250A AC. The output voltage changes proportionally to the measured current under operating conditions as specified by the manufacturer.
The 333mV AC output signal can be used with meters or measuring devices that have an input for CTs rated at 333mV, provided that the CT ratio is set correctly to 250A/333mV to ensure accurate current measurement.
Installation and Usage
- Select the alternating conductor where you want to measure the current.
- Disconnect power supply and verify there is no voltage before installation.
- Open the split core and install it around a single wire of the circuit that needs measurement.
- Cover the CT core completely according to the locking mechanism of the device.
- Connect signal wires to meters supporting 333mV AC CT input.
- Set the CT Ratio or CT Rating in the measuring device to match 250A/333mV.
- Check installation direction and polarity from the manufacturer's documentation.
Examples and Usage Guidelines
- Measure electrical current in control panels and power distribution cabinets
- Works with Energy Monitoring systems supporting 333mV CT input
- Measures load currents of machinery and industrial electrical equipment
- Adaptable for building energy consumption monitoring systems
- Used with current measurement systems requiring open-CT installation
Important Considerations
- This model is a 333mV AC output CT, not a 5A output CT
- Meters or measuring devices supporting 333mV AC input must be used in conjunction with it
- Check the current rating and measurement range to match actual usage requirements
- Ensure that the CT core size is appropriate for the wire gauge or bus bar size
- For general load current measurements, wrap the CT around a single conductor only, not around phase and neutral wires together
- Check CT Ratio settings and signal terminals before use
- Some technical data references KCTM-24V Series; installation documentation for specific models should be reviewed beforehand
- Installation in electrical systems must be carried out by qualified personnel following proper electrical safety measures