KEPLER KCTM-24 V Split Core Current Transformer
KEPLER KCTM-24 V Split Core Current Transformer is a detachable core (Split Core CT) current transformer for measuring alternating current in electrical systems. It has a primary rated current of 150A and an output of 333mV AC at the rated current, suitable for use with current measurement devices or meters that support a 333mV AC CT input.
The device is designed to allow opening and closing of the transformer core, making it easy to install around the electrical conductor without needing to disconnect the wires from their original connection points. However, installation must follow appropriate electrical safety measures.
Model KCTM-24 V belongs to the KEPLER KCTM-24V Series and provides an output signal of 333mV AC, which differs from a transformer with a 5A output. Therefore, it should be used in conjunction with devices that support this type of output.
General Features
- Brand: KEPLER
- Product Model: KCTM-24 V
- Product Type: Split Core Current Transformer
- Detachable core current transformer, can open the core for installation around electrical conductors.
- Rated primary current: 150A AC
- Rated output voltage: 333mV AC
- Precision: Class 0.5 according to series catalog data
- Supports frequency range: 50-60Hz
- Housing made of PC / UL94-V0 material, as per series information
- Suitable for current measurement and energy consumption monitoring systems.
Technical Specifications (Technical Specifications)
| Brand |
KEPLER |
| Model |
KCTM-24 V |
| Product Series |
KCTM-24V Series |
| Product Type |
Split Core Current Transformer |
| Rated Primary Current |
150A AC |
| Rated Output |
333mV AC |
| Accuracy Class |
Class 0.5 (Series Reference) |
| Frequency |
50-60Hz |
| Phase Angle |
Less than 2 degrees at 50% of rated current (Series Reference) |
| Insulation Voltage |
600VAC (Series Reference) |
| Maximum Primary Voltage |
5000VAC, Insulated Conductor (Series Reference) |
| Dielectric Strength |
2.5kV / 1mA / 1min (Series Reference) |
| Operating Temperature |
-15 to +60°C |
| Operating Humidity |
Less than 85% RH |
| Case Material |
PC / UL94-V0 |
| Bobbin Material |
PBT |
| Core Material |
Permalloy |
| Internal Structure |
Epoxy |
| Lead Wire |
UL1015, Twisted Pair, 22 AWG (Series Reference) |
| Compatible Measurement Input |
333mV AC CT Input |
How It Works
The Split Core Current Transformer operates based on the principle of electromagnetic induction. When alternating current flows through a conductor within the CT core, it generates a magnetic field that induces an electrical signal in the secondary winding.
For model KCTM-24 V with a rating of 150A/333mV, the device is designed to have an output voltage rating of 333mV AC when there is a primary current of 150A AC. The output voltage changes proportionally with the measured current under operating conditions as specified by the manufacturer.
The 333mV AC output signal can be used with meters or measuring devices that have an input for CTs rated at 333mV, provided that the CT ratio is set to match 150A/333mV to ensure accurate current measurement.
Installation and Usage
- Select the alternating conductor where you want to measure the current.
- Install the CT by clamping it around a single wire of the circuit that needs to be measured.
- Closure the split core completely according to the locking mechanism of the device.
- Connect the signal wires to a meter that supports 333mV AC CT input.
- Set the CT Ratio or CT Rating in the measuring equipment to match 150A/333mV.
Check the installation direction and signal polarity from the manufacturer's documentation
Follow the steps to isolate power sources and safety measures before installation
Examples and Usage Guidelines
- Measure electrical current in control panels and distribution boards
- Use with Energy Monitoring systems that support a 333mV CT input
- Measure the load current of machinery and industrial electrical equipment
- Apply in building energy consumption monitoring systems
- Use in systems requiring current measurement by installing split-core CTs
Considerations
- This model is a 333mV AC output CT, not a 5A output CT
- Meters or measuring devices that support a 333mV AC input must be used in conjunction with it
- Check the current rating and measurement range to match actual usage requirements
- Verify the CT core size fits the wire gauge before installation
- Cover only one conductor with the CT for general load current measurements, not both phase and neutral wires together
- Ensure correct CT Ratio settings and signal polarity are configured prior to use
- Some technical data references KCTM-24V Series; check specific model documentation before installation
- High voltage electrical system installations must be carried out by qualified personnel following electrical safety measures