KEPLER KCTM-24 V Split Core Current Transformer with Primary Rating 100A/333mV
KEPLER KCTM-24 V Split Core Current Transformer is a current transformer designed for measuring alternating current in electrical systems, featuring a primary rating of 100A and an output voltage of 333mV AC at rated current. It is suitable for use with measurement devices or meters that support CT input of 333mV AC.
The device is designed to allow the transformer core to be opened and closed, enabling easy installation around wires without needing to disconnect them from their original connections. Installation must follow electrical safety procedures.
Model KCTM-24 V belongs to the KEPLER KCTM-24V Series with an output voltage of 333mV AC, differing from transformers that have a 5A output. Therefore, it is important to select compatible signal receiving equipment.
General Features
- Brand: KEPLER
- Product Model: KCTM-24 V
- Product Type: Split Core Current Transformer
- Removable core design allows for easy installation around wires without disconnecting them.
- Rated Primary Current: 100A AC
- Rated Output Voltage: 333mV AC
- Catalog accuracy class: Class 0.5
- Suitable for frequency range: 50-60Hz
- Housing material: PC / UL94-V0 (Series Reference)
- Designed for current measurement and energy monitoring systems.
Technical Specifications
| Brand |
KEPLER |
| Model |
KCTM-24 V |
| Product Series |
KCTM-24V Series |
| Product Type |
Split Core Current Transformer |
| Rated Primary Current |
100A AC |
| Rated Output |
333mV AC |
| Accuracy Class |
Class 0.5 (Series Reference) |
| Frequency |
50-60Hz |
| Phase Angle |
Less than 2 degrees at 50% of rated current (Series Reference) |
| Insulation Voltage |
600VAC (Series Reference) |
| Maximum Primary Voltage |
5000VAC, Insulated Conductor (Series Reference) |
| Dielectric Strength |
2.5kV / 1mA / 1min (Series Reference) |
| Operating Temperature |
-15 to +60°C |
| Operating Humidity |
Less than 85% RH |
| Case Material |
PC / UL94-V0 |
| Bobbin Material |
PBT |
| Core Material |
Permalloy |
| Internal Structure |
Epoxy |
| Lead Wire |
UL1015 Twisted Pair, 22 AWG (Series Reference) |
| Compatible Measurement Input |
333mV AC CT Input |
How It Works
The Split Core Current Transformer operates based on the principle of electromagnetic induction. When alternating current flows through a conductor within the CT core, it generates a magnetic field that induces signals in the secondary winding.
For the KCTM-24 V model with a rating of 100A/333mV, the device is designed to have an output voltage rating of 333mV AC when there is a primary current of 100A AC. The output voltage changes proportionally with the measured current under the operating conditions specified by the manufacturer.
The 333mV AC output signal can be used with meters or measuring devices that have an input for CTs rated at 333mV, provided the CT ratio is set to match 100A/333mV.
Installation and Usage
- Select the alternating current conductor you wish to measure the current of.
- Install the CT by clamping it around a single wire in the circuit that needs to be measured.
- Closed the split core completely according to the locking mechanism of the device.
- Connect the output signal wires to measuring devices that support 333mV AC input.
- Set the CT Ratio on the meter or controller to match 100A/333mV.
- Check the installation direction and polarity according to the manufacturer's documentation.
- Follow safety procedures for disconnecting power sources before installing the device.
Usage Examples and Guidelines
- Measure electrical current in control panels and distribution boards.
- Use with energy analysis and monitoring devices.
- Monitor the load current of machinery and industrial electrical systems.
- Used in Energy Monitoring systems that support 333mV CT input.
- Adapted for current measurement systems requiring open-core CT installation.
Considerations
- This model is a 333mV AC output CT, not a 5A output CT.
- Must be used with measuring devices that support 333mV AC input.
- Check the current rating and measurement range to match the actual system current.
- Verify the CT core size matches the wire or busbar size.
- Cover only one conductor with the CT for general load current measurement, not both phase and neutral wires together.
- Ensure CT Ratio settings and polarity are correctly configured before use.
- Some technical data references KCTM-24V Series; installation documentation should be reviewed prior to installation.
- Installation near high-current or high-voltage circuits must be performed by qualified personnel following safety measures.