KEPLER KAQ-55 Series Fixed Gas Detector (Fixed Gas Detector)
KEPLER KAQ-55 Series Fixed Gas Detector is a fixed gas detector for measuring gas concentration in industrial and environmental monitoring applications. It has sub-models for detecting oxygen (O2), carbon monoxide (CO), hydrogen sulfide (H2S), and combustible gas (Combustible Gas / LEL)
The device can select signal interface according to the model, including 4-20 mA analog current output or digital communication RS485, suitable for connecting to gas control and monitoring systems such as PLC, gas monitor systems, and alarm control units that support device signals
KAQ-55 Series uses 24VDC ±25% power supply, consumes less than 2W of power, and has an IP66 dust and water protection rating. The plastic housing is designed for wall mounting, with dimensions of 165 x 118 x 62 mm and a weight of approximately 0.5 kg
Important: The KAQ-55 Series is suitable for installation areas that do not require explosion-proof equipment (Non-Explosion-Proof Area) according to the catalog information, so it is necessary to check the classification of hazardous areas before selecting and using
General Features
- Brand: KEPLER
- Product Series: KAQ-55 Series
- Product Type: Fixed Gas Detector
- Select gas types to be measured according to the model: O2, CO, H2S, or Combustible Gas (LEL)
- Uses Electrochemical sensor for gases O2, CO, and H2S
- Uses Catalytic sensor for combustible gas (LEL)
- Detects gas using Natural Diffusion method
- Has 4-20 mA analog output model
- Has digital communication RS485 model
- The 4-20 mA model has 2 configurable relay outputs
- Uses DC 24V ±25% power supply
- Consumes less than 2W of power
- Has dust and water protection rating IP66
- Wall mounted (Wall Mounted)
- Compact plastic housing
- Suitable for installation areas without explosion protection requirements
Model Selection Guide (Model Selection Guide)
| Model |
Measuring Gas |
Measuring Range |
Signal Output |
| KAQ-55OA |
Oxygen (O2) |
0-25% Vol |
4-20 mA |
| KAQ-55OR |
Oxygen (O2) |
0-25% Vol |
RS485 |
| KAQ-55CA |
Carbon Monoxide (CO) |
0-500 ppm |
4-20 mA |
| KAQ-55CR |
Carbon Monoxide (CO) |
0-500 ppm |
RS485 |
| KAQ-55HA |
Hydrogen Sulfide (H2S) |
0-100 ppm |
4-20 mA |
| KAQ-55HR |
Hydrogen Sulfide (H2S) |
0-100 ppm |
RS485 |
| KAQ-55LA |
Combustible Gas (LEL) |
0-100% LEL |
4-20 mA |
| KAQ-55LR |
Combustible Gas (LEL) |
0-100% LEL |
RS485 |
Note: One unit detects gas according to the selected model and has signal output according to the product code. It does not support both 4-20 mA and RS485 simultaneously on every unit.
Technical Specifications
| Specifications |
Details |
| Brand | KEPLER |
| Series | KAQ-55 Series |
| Product Type | Fixed Gas Detector |
| Detected Gas | O2 / CO / H2S / Combustible Gas (Depending on Model) |
| O2 Measuring Range | 0-25% Vol |
| CO Measuring Range | 0-500 ppm |
| H2S Measuring Range | 0-100 ppm |
| Combustible Gas Range | 0-100% LEL |
| O2 Resolution | 0.1% Vol |
| CO Resolution | 1 ppm |
| H2S Resolution | 1 ppm |
| LEL Resolution | 1% LEL |
| Sensor Type (O2 / CO / H2S) | Electrochemical |
| Sensor Type (LEL) | Catalytic |
| Measuring Method | Natural Diffusion |
| Response Time (O2 / Toxic Gas) | T90 ≤ 60 Seconds |
| Response Time (Combustible) | T90 ≤ 30 Seconds |
| Sensor Life (O2) | 1 Year (Catalog Reference) |
| Sensor Life (CO / H2S / LEL) | 2 Years (Catalog Reference) |
| Analog Signal Output | 4-20 mA (A Models) |
| Digital Communication | RS485 (R Models) |
| Alarm Relay Output | 2 Programmable Relays for 4-20 mA Type |
| 4-20 mA Wiring | 3-Wire Shielded Cable, 1.5 mm2 |
| RS485 Wiring | 4-Wire Shielded Cable, 1.5 mm2 |
| Maximum Cable Distance | 1,000 m (Subject to Installation Conditions) |
| Mounting | Wall Mounted |
| Operating Temperature (O2 / Toxic Gas) | -20 to +50°C |
| Operating Temperature (Combustible) | -40 to +70°C |
| Operating Humidity | <95% RH, Non-Condensing |
| Power Supply | 24VDC +25% |
| Power Consumption | <2W |
| Housing Material | Plastic |
| Ingress Protection | IP66 |
| Approval Listed in Catalog | CE |
| Dimensions | 165 x 118 x 62 mm |
| Weight | Approximately 0.5 kg |
| Installation Area | Non-Explosion-Proof Area |
Gas Detection Details
Oxygen (O2) Detector
Models KAQ-55OA and KAQ-55OR are used to measure oxygen levels in air in the range of 0-25% Vol with a resolution of 0.1% Vol. They use an Electrochemical sensor and are suitable for monitoring oxygen levels in industrial areas that require monitoring of abnormally low or high oxygen conditions.
Carbon Monoxide (CO) Detector
Models KAQ-55CA and KAQ-55CR are used to measure carbon monoxide gas in the range of 0-500 ppm with a resolution of 1 ppm. They use an Electrochemical sensor and are suitable for areas with combustion, engines, furnaces, and production processes that may generate CO.
Hydrogen Sulfide (H2S) Detector
Models KAQ-55HA and KAQ-55HR are used to measure hydrogen sulfide gas in the range of 0-100 ppm with a resolution of 1 ppm. They use an Electrochemical sensor and are suitable for wastewater treatment systems, drainage systems, and industrial processes that are at risk of H2S gas.
Combustible Gas (LEL) Detector
Models KAQ-55LA and KAQ-55LR are used to measure flammable gas in the range of 0-100% LEL with a resolution of 1% LEL. They use a Catalytic sensor and are suitable for monitoring the accumulation of flammable gas in environments where the manufacturer allows installation, but the target gas type and reference gas used for calibration must be checked.
4-20 mA Output Signal System
Models with the suffix A support the 4-20 mA analog output signal for transmitting measurement data to PLC, Gas Controller, or control systems with appropriate current input.
According to the catalog, the 4-20 mA models have two configurable relay outputs. Before actual use, the contact ratings and relay operation characteristics must be checked from the manual.
The catalog recommends using a 3-Wire Shielded Cable with a size of 1.5 mm2 and a maximum cable length of 1,000 meters. However, the actual usable distance depends on the supply voltage, environmental conditions, installation, and electrical properties of the system.
RS485 Communication System
Models with the suffix R support digital RS485 communication for connecting to control systems that support the same interface, such as PLC, gas monitoring systems, or SCADA systems.
The catalog recommends using a 4-Wire Shielded Cable with a size of 1.5 mm2 and a maximum cable length of 1,000 meters. Before system design, the communication protocol, data transfer rate, device configuration, and wiring format must be checked from the specific model manual.
Having an RS485 interface does not automatically confirm that the device supports Modbus RTU. The communication protocol must be checked before designing the control system.
Operating Principle of Fixed Gas Detector
KAQ-55 Series detects gas using the Natural Diffusion principle, where gas from the environment diffuses into the sensor's gas sensing section, and then the device processes the sensor's response into a signal to send to the connected control or display system
The O2, CO, and H2S groups use Electrochemical sensors, while the flammable gas group uses Catalytic sensors, which have different limitations in terms of gas type and environmental conditions
Detection performance depends on installation location, air circulation, sensor condition, calibration, and type of target gas
Installation and Usage Guidelines
- Select the sub-model that matches the gas type to be detected
- Select 4-20 mA or RS485 output that matches the control system
- Check that the installation area does not require the use of explosion-proof certified equipment
- Install the unit on a wall or sturdy structure according to the manufacturer's manual
- Select the installation location based on gas dispersion characteristics, ventilation, and risk assessment
- Use a suitable 24VDC power supply according to the equipment's specifications and ratings
- Run shielded signal wiring and manage the grounding system according to the manual
- Check the terminal diagram and output specifications before connecting to the PLC or Gas Controller system
- Adjust the alarm level in the control system to be appropriate for the gas type and safety requirements
- Perform calibration and test the device's response according to the manual before starting operation
- Plan for sensor inspection and replacement when the service life is complete or when test results are not passed
Examples and Usage Guidelines
- Gas detection system within an industrial plant
- Monitoring oxygen levels in work areas
- CO detection system in areas with engines or combustion processes
- H2S detection system within a wastewater treatment plant
- Flammable gas detection system in areas that do not require explosion-proof equipment
- Gas detection system connected to a PLC or alarm control unit
- Environmental control and monitoring systems in buildings or factories
- Maintenance and inspection of permanently installed gas detection systems
Safety Considerations
- KAQ-55 Series is a fixed installation gas detection device, not a portable gas detector
- Each model supports specific gas types and outputs according to the product code; select the model that matches the application
According to the catalog, the equipment is suitable for environments that do not require Explosion-Proof devices
IP66 standard does not mean that the device is certified for use in explosive areas
Check the RS485 protocol and wiring diagram from the manual before designing the system
Check the contact rating of the relay before connecting to the load or alarm circuit
Catalytic sensors for flammable gases may be affected by low oxygen or substances that cause sensor degradation
Calibration and testing of response must be carried out at specified intervals to maintain system reliability
Using the equipment in high-risk safety systems must consider the overall system requirements and appropriate contingency measures
Check the product certification, components, and warranty details with the supplier before ordering