SG-VB-4T037G/045P, SANGI, SG-VB Series, Inverter, Three-phase motor control inverter with power ratings of 37 kW/50 HP for load G and 45 kW/60 HP for load P. Input voltage: three-phase 380VAC ±15%, frequency: 50/60Hz. Supports V/F Control, Torque Control, and RS485 Modbus communication for machinery, pumps, and fans.
The SG-VB-4T037G/045P from the brand SANGI is an inverter in the SG-VB series for controlling the speed of a three-phase motor. It supports motor power of 37 kW or 50 HP for load type G and 45 kW or 60 HP for load type P, where G is used with constant torque loads and P is used with variable torque fan-type loads.
It operates on three-phase input voltage of 380VAC ±15%, frequency 50/60Hz. It supports V/F control and Torque Control modes along with inputs and outputs for connecting to a control system, including RS485 Modbus communication. Suitable for machinery, pump systems, fan systems, and conveyor belt systems by selecting the appropriate rating based on load characteristics.
Key Features
Controls speed of three-phase motor
Suitable for 37 kW loads (G type) and 45 kW loads (P type)
Supports V/F Control and Torque Control modes
RS485 Modbus communication supported
Digital and analog inputs for control commands reception
Digital and analog outputs for connecting devices
Used in machinery, pumps, fans, and conveyor belt systems
Tech Specifications
Brand: SANGI
Model: SG-VB-4T037G/045P
Series: SG-VB
Type: Inverter for three-phase motor
Power rating for load G: 37 kW / 50 HP
Power rating for load P: 45 kW / 60 HP
Load type G: Constant torque load
Load type P: Variable torque fan-type load
Input voltage: Three-phase 380VAC ±15%
Input frequency: 50/60Hz
Input current rating for G/P: 76/92 A
Output current rating for G/P: 75/91 A
Series output voltage range for 380V system: Three-phase 0–380VAC
Control modes: V/F Control / Torque Control
V/F design frequency range of the series: 0–1000Hz
SVC design frequency range of the series: 0–320Hz
G type starting torque: 0.5Hz / 150% when using SVC
P type starting torque: 0.5Hz / 100%
Overload capacity for G type: 150% of rated current for 60 seconds and 180% of rated current for 1 second
Overload capacity for P type: 120% of rated current for 60 seconds and 150% of rated current for 1 second
Digital inputs in the series: 6 channels, NPN type
Analog inputs in the series: 2 channels, supports 0–10V and 4–20mA
Digital outputs in the series: Contact NO/NC and 1 channel, NPN type
Analog output in the series: 1 channel, supports 0–10V and 4–20mA
Communication: RS485 Modbus
Applications
Speed control of motors in industrial machinery
Pump system control by selecting the appropriate rating based on load characteristics
We use cookies to make the site work properly, to understand how it is used, and to show content that is relevant to you. You choose which types to allow; strictly necessary cookies are always on. Privacy Policy