SG-VB-4T055G/075P, SANGI, SG-VB Series, Inverter, Three-phase motor control inverter with power ratings of 55 kW/70 HP for load G and 75 kW/100 HP for load P. Input voltage: three-phase 380VAC ±15%, frequency: 50/60Hz. Supports V/F Control, Torque Control, and RS485 Modbus communication for machinery, pumps, and fans.
The SG-VB-4T055G/075P from the brand SANGI is an inverter in the SG-VB series for controlling the speed of a three-phase motor. It supports motor power up to 55 kW or 70 HP for load type G and 75 kW or 100 HP for load type P, where G is used with constant torque loads and P is suitable for variable torque loads such as fans.
It operates on three-phase input voltage of 380VAC ±15% at a frequency of 50/60Hz. It supports V/F control and Torque Control along with inputs and outputs for connecting to the control system, including RS485 Modbus communication. Suitable for machinery, pump systems, fan systems, and conveyor belt applications by selecting the appropriate rating based on load characteristics.
Key Features
Controls speed of three-phase motor
Suitable for 55 kW loads (G) and 75 kW loads (P)
Supports V/F Control and Torque Control
RS485 Modbus communication supported
Digital and analog inputs for control commands reception
Digital and analog outputs for connecting devices
Used in machinery, pumps, fans, and conveyor belt systems
Tech Specifications
Brand: SANGI
Model: SG-VB-4T055G/075P
Series: SG-VB
Type: Inverter for three-phase motor
Power rating for load G: 55 kW / 70 HP
Power rating for load P: 75 kW / 100 HP
Load type G: Constant torque load
Load type P: Variable torque load / Fan Type
Input voltage: Three-phase 380VAC ±15%
Input frequency: 50/60Hz
Input current rating for G/P: 113/157 A
Output current rating for G/P: 112/150 A
Series output voltage range for system 380V: Three-phase 0–380VAC
Control mode: V/F Control / Torque Control
V/F series design frequency range: 0–1000Hz
SVC series design frequency range: 0–320Hz
G type starting torque: 0.5Hz / 150% when using SVC
P type starting torque: 0.5Hz / 100%
Overload capacity for G type: 150% of rated current for 60 seconds and 180% of rated current for 1 second
Overload capacity for P type: 120% of rated current for 60 seconds and 150% of rated current for 1 second
Digital inputs in series: 6 channels, NPN type
Analog inputs in series: 2 channels, supports 0–10V and 4–20mA
Digital outputs in series: Contact NO/NC and 1 channel of NPN type
Analog output in series: 1 channel, supports 0–10V and 4–20mA
Communication: RS485 Modbus