KEPLER KCTM-36 V Split Core Current Transformer
KEPLER KCTM-36 V Split Core Current Transformer is a detachable core (Split Core CT) current transformer for measuring alternating current in electrical systems. It has a primary rated current of 600A and an output voltage rating of 333mV AC, suitable for use with electricity metering devices and current measurement equipment that support a 333mV AC input.
The split core design allows the transformer's core to be opened and closed to install around electrical conductors without needing to disconnect existing wire ends from their connections. This increases installation convenience for current measurement systems, although power sources should be disconnected and safety measures followed before installation.
KEPLER KCTM-36 V belongs to the KCTM-36V Series, which is a 333mV AC output voltage type current transformer, differing from the KCTM-36 model with a 5A output current. Therefore, appropriate signal receiving equipment and current rating settings must be selected according to the CT type.
General Features
- Brand: KEPLER
- Product Model: KCTM-36 V
- Product Type: Split Core Current Transformer
- Detachable core current transformer, can open the core to install around electrical conductors
- Rated primary current: 600A AC
- Rated output voltage: 333mV AC
- Precision: Class 0.5 according to series data
- Supports power frequency: 50-60Hz
- Housing made of PC / UL94-V0 material
- Suitable for current measurement and electricity consumption monitoring systems
Technical Specifications (Technical Specifications)
| Brand | KEPLER |
| Model | KCTM-36 V |
| Product Series | KCTM-36V Series |
| Product Type | Split Core Current Transformer |
| Rated Primary Current | 600A AC |
| Rated Output | 333mV AC |
| Accuracy Class | Class 0.5 (Series Reference) |
| Accuracy Range | 20% to 120% of Rated Current (Series Reference) |
| Frequency | 50-60Hz |
| Phase Angle | Less than 2 degrees at 50% of rated current (Series Reference) |
| Insulation Voltage | 600VAC (Series Reference) |
| Maximum Primary Voltage | 5000VAC, Insulated Conductor (Series Reference) |
| Dielectric Strength | 2.5kV / 1mA / 1min (Series Reference) |
| Operating Temperature | -15 to +60°C |
| Operating Humidity | Less than 85% RH |
| Case Material | PC / UL94-V0 |
| Bobbin Material | PBT |
| Core Material | Permalloy |
| Internal Structure | Epoxy |
| Lead Wire | UL1015, Twisted Pair, 22 AWG (Series Reference) |
| Compatible Measurement Input | 333mV AC CT Input |
How It Works
A split core current transformer operates based on the principle of electromagnetic induction. When alternating current flows through a conductor within the CT core, it generates a magnetic field that induces an electrical signal in the secondary winding.
The KEPLER KCTM-36 V with a rating of 600A/333mV is designed to have an output voltage rating of 333mV AC when the primary current equals 600A AC. The output signal varies proportionally with the measured current under conditions specified by the manufacturer.
The 333mV AC output voltage can be used in conjunction with measuring devices that support CT output voltage, provided that the CT rating is set to match 600A/333mV on the receiving device for accurate current measurement.
Installation and Usage
- Select the alternating current conductor where you want to measure the current.
- Disconnect power supply and ensure there is no voltage before installation.
- Open the split core and install it around a single wire of the circuit that needs measurement.
- Cover the CT core completely according to the locking mechanism of the device.
- Connect the signal wires to a meter supporting 333mV AC CT input.
- Set the CT rating in the measuring device to match 600A/333mV.
Check the installation direction and signal polarity from the manufacturer's documentation
Ensure that the CT core channel size is appropriate for the wire or bus bar size
Examples and Usage Guidelines
- Measure electrical current in control panels and distribution boards
- Use with Energy Monitoring systems supporting 333mV CT input
- Monitor load currents of machinery and industrial equipment
- Apply in building energy consumption monitoring systems
- Use for current measurement applications requiring open-CT installation
Considerations
- This model is a 333mV AC output CT, not a 5A output CT
- Meters or measuring devices supporting 333mV AC CT input must be used in conjunction with it
- Verify the current rating and measurement range to match actual usage requirements
- For general load current measurements, encircle only one conductor with the CT, not both phase and neutral wires together
- Check the CT core channel size and installation space before selecting for use
- Configure CT Rating settings and signal polarity prior to operation
- Avoid using 333mV CTs as direct replacements for 5A CTs
- Some technical data references KCTM-36V Series; consult specific model documentation before installation
- Installation in electrical systems must be carried out by qualified personnel following safety measures